Reference Manual
00809-0100-4001, Rev JA
Appendix A: Reference Data
November 2012
Specifications and reference data
Output Code F and W
If self-diagnostics detect a gross transmitter failure, that information gets passed as a status
along with the process variable.
A.2.16 Temperature Limits
Table A-5. 3051 process temperature limits
Ambient
–40 to 185 °F (–40 to 85 °C)
With LCD display
(1)
: –40 to 175 °F (–40 to 80 °C)
Storage
–50 to 230 °F (–46 to 110 °C)
With LCD display: –40 to 185 °F (–40 to 85 °C)
Process
At atmospheric pressures and above. See Table A-5
(1) LCD display may not be readable and LCD updates will be slower at temperatures below -4 °F (-20 °C).
3051CD, 3051CG, 3051CA
Silicone Fill Sensor
(1)
with Coplanar Flange –40 to 250 °F (–40 to 121 °C)
(2)
with Traditional Flange –40 to 300 °F (–40 to 149 °C)
(2)(3)
with Level Flange –40 to 300 °F (–40 to 149 °C)
(2)
with 305 Integral Manifold –40 to 300 °F (–40 to 149 °C)
(2)
Inert Fill Sensor
(1)
-40 to 185 °F (–40 to 85 °C)
(4)(5)
3051H (process fill fluid)
D.C.
®
Silicone 200
(1)
–40 to 375 °F (–40 to 191 °C)
Inert
(1)
–50 to 350 °F (–45 to 177 °C)
Neobee M-20
®(1)
0 to 375 °F (–18 to 191 °C)
3051T (process fill fluid)
Silicone Fill Sensor
(1)
–40 to 250 °F (–40 to 121 °C)
(2)
Inert Fill Sensor
(1)
–22 to 250 °F (–30 to 121 °C)
(2)
3051L low-side temperature limits
Silicone Fill Sensor
(1)
–40 to 250 °F (–40 to 121 °C)
(2)
Inert Fill Sensor
(1)
0 to 185 °F (–18 to 85 °C)
(2)