114
Reference Manual
00809-0100-4001, Rev JA
Appendix A: Reference Data
November 2012
Specifications and reference data
Table A-4. 3051L and level flange rating limits
A.2.13 Static Pressure Limit
Rosemount 3051CD Only
Operates within specifications between static line pressures of 0.5 psia and 3626 psig (4500
psig (310, 3 bar) for
Option Code P9).
Range 0: 0.5 psia and 750 psig (3, 4 bar and 51, 7 bar)
Range 1: 0.5 psia and 2000 psig (3, 4 bar and 137, 9 bar)
A.2.14 Burst Pressure Limits
Burst pressure on Coplanar, traditional, or 3051H process flange is 10000 psig (69 MPa).
Burst pressure for the 3051T is:
Ranges 1–4: 11000 psi (75,8 MPa)
Range 5: 26000 psig (179 MPa)
A.2.15 Failure Mode Alarm
Output Code A
If self-diagnostics detect a gross transmitter failure, the analog signal will be driven either below
3.75 mA or to 21.75 mA to alert the user. NAMUR-compliant values are available, option code
C4. High or low alarm signal is user-selectable by internal jumper.
Output Code M
If self-diagnostics detect a gross transmitter failure, the analog signal will be driven either below
0.94 V or above 5.4 V to alert the user (below 0.75 V or above 4.4 V for Option C2). High or low
alarm signal is user-selectable by internal jumper.
Standard Type CS rating SST rating
ANSI/ASME Class 150 285 psig 275 psig
ANSI/ASME Class 300 740 psig 720 psig
ANSI/ASME Class 600 1480 psig 1440 psig
At 100 °F (38 °C), the rating decreases with
increasing temperature.
DIN PN 10–40 40 bar 40 bar
DIN PN 10/16 16 bar 16 bar
DIN PN 25/40 40 bar 40 bar
At 248 °F (120 °C), the rating decreases
with increasing temperature.