Emerson 3051S Specifications Page 32

  • Download
  • Add to my manuals
  • Print
  • Page
    / 222
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 31
22
Reference Manual
00809-0100-4001, Rev JA
Section 2: Installation
November 2012
Installation
2.9 Electrical considerations
Note
Make sure all electrical installation is in accordance with national and local code requirements.
2.9.1 Conduit installation
Recommended conduit connections are shown in Figure 2-15.
Figure 2-15. Conduit installation diagrams.
If all connections are not sealed, excess moisture accumulation can damage the
transmitter. Make sure to mount the transmitter with the electrical housing positioned
downward for drainage. To avoid moisture accumulation in the housing, install wiring with
a drip loop, and ensure the bottom of the drip loop is mounted lower than the conduit
connections or the transmitter housing.
Sealing
Compound
Conduit
Lines
CORRECT
Possible
Conduit Line
Positions
Sealing
Compound
Possible
Conduit Line
Positions
CORRECT INCORRECT
Page view 31
1 2 ... 27 28 29 30 31 32 33 34 35 36 37 ... 221 222

Comments to this Manuals

No comments