Emerson 3051S Specifications Page 104

  • Download
  • Add to my manuals
  • Print
  • Page
    / 222
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 103
94
Reference Manual
00809-0100-4001, Rev JA
Section 5: Troubleshooting
November 2012
Troubleshooting
Span Fail
The span value, set with the local span adjustment button, exceeds the maximum rangedown
allowed for a particular range, or the pressure sensed by the transmitter exceeds the sensor
limits.
Local Dsbld
This message appears during reranging with the integral zero and span buttons and indicates
that the transmitter local zero and span adjustments have been disabled. The adjustments may
have been disabled by the transmitter security jumper on the transmitter circuit board or
through software commands from the Field Communicator. See “Security (write protect)” on
page 20 for information on the position of the security jumper and information on software
lockout.
Write Protect
This message appears if you attempt to change the transmitter configuration data while the
security jumper is in the ON position. See “Security (write protect)” on page 20 for more
information about the security jumper.
Field communicator diagnostics
Tab le 5 -2 is a list of messages used by the Field Communicator (HC) and their corresponding
descriptions.
Variable parameters within the text of a message are indicated with <variable parameter>.
Reference to the name of another message is identified by
[another message].
Table 5-2. Field communicator messages
Message Description
1k snsr EEPROM
error-factory ON
Replace the transmitter
1k snsr EEPROM
error-user-no out ON
Use the Field Communicator to reset the following
parameters: remote seal isolator, remote seal fill fluid,
flange material, o-ring material, transmitter type, remote
seal type, flange type, meter type, number of remote
seals.
1k snsr EEPROM
error-user ON
Perform a full trim to recalibrate the transmitter.
4k micro EEPROM
error-factory ON
Replace the electronics board.
4k micro EEPROM
error-user-no out ON
Use the Field Communicator to reset the message field.
4k micro EEPROM
error-user ON
Use the Field Communicator to reset the following
parameters: units, range values, damping, analog output,
transfer function, tag, scaled meter values. Perform a D/A
trim to ensure that the error is corrected.
Page view 103
1 2 ... 99 100 101 102 103 104 105 106 107 108 109 ... 221 222

Comments to this Manuals

No comments