4.1.3 Teamwork Mode 1
Teamwork Mode 1 works best in small rooms with balanced heat loads. The return temperature and
humidity sensor readings of all units in operation (fan on) are averaged by the master unit, Unit #1,
and used for control. The master unit will send the operating requirements to all operating units
according to unit numbers, rotated by one unit every 24 hours.
In this teamwork mode, most of the parameters are shared; if set in any one of the units, all other
units will follow with the same settings. AutoSet will adjust the proportional band in Teamwork
Mode 1, see 3.2.1 - Temperature Proportional Band.
The master unit evenly divides the system proportional band among the number of available units.
Each unit will receive instruction on how to operate from the master unit based on how far the system
deviates from the setpoints.
The number of available units is calculated like:
In non-standby configuration: all units with fan on
In typical standby function (no cascade): all units with fan on
In cascade mode: all units that could operate (no alarm, which forces the unit to switch off, unit
not switched off, etc.)
Figure 28 shows how two cooling units work together in Teamwork Mode 1. Since Unit 1 and Unit 2
are available to operate, the master unit, Unit 1, averages the temperature and humidity sensor
readings from each unit.
The master unit determines that a 60% call for cooling is required for the system. Since there are two
available cooling units, each unit makes up half of the system proportional band; Unit 1 handles 0-
50% system call for cooling and Unit 2 handles 51-100%. For every 1% system call for cooling, each
unit provides 2% of its total cooling capacity.
The 60% system call for cooling exceeds the 50% Unit 1 can provide, so Unit 1 operates at full
capacity. The remaining 10% system call for cooling (60% - 50% = 10%) is handled by Unit 2. Unit 2
responds by operating at 20% cooling capacity (50% ÷ 10% = 20%).
Figure 28 Teamwork Mode 1 with two cooling units
NOTE
1. Proportional actuators (chilled water valve, free-cooling actuator) are driven in parallel in
all units.
2. Changeover to second cooling source, low limit during dehumidification and low supply
limit control air local functions, managed from each unit independently.
C1 C2
cooling
+100 %
0%
1/2 Proportional Band
+temp.
Unit 2 Deviation : 20%
Setpoint
C1 C2
cooling
+100%
0%
1/2 Proportional Band
+temp.
Setpoint
0%
Setpoint
- temp.
-100 %
+temp.
1/2 Proportional Band +100%
1/2 Proportional Band
heating
100 %
60%
0%
System Deviation : 60%
System proportional band
Unit 1 Deviation : 100%