Service Menu Parameters
85
Figure 73 Set alarms screen, page 4 of 8
Figure 74 Set alarms screen, page 5 of 8
SET ALARMS (page 4 of 8)
PASSWORD (Actual Level 0) ????
DELAY EN-DIS TYPE
MAIN FAN OVERLOAD 5 ENABLE ALM
LOSS OF AIRFLOW 30 ENABLE ALM
CLOGGED FILTERS 2 ENABLE WRN
HIGH ROOM TEMP 30 ENABLE WRN
LOW ROOM TEMP 30 ENABLE WRN
HIGH ROOM HUM 30 ENABLE WRN
LOW ROOM HUM 30 ENABLE WRN
HIGH TEMP SENSOR A 30 DISAB WRN
LOW TEMP SENSOR A 30 DISAB WRN
HIGH HUM SENSOR A 30 DISAB WRN
LOW HUM SENSOR A 30 DISAB WRN
S234
S235
S236
S237
S238
S239
S240
S241
S242
S243
S244
S245
S246
UNIT 01
SET ALARMS (page 5 of 8)
PASSWORD (Actual Level 0) ????
DELAY EN-DIS TYPE
COMP 1 OVERLOAD ENABLE ALM
COMP 2 OVERLOAD ENABLE ALM
COMP 1 HIGH PRESSURE ENABLE ALM
COMP 2 HIGH PRESSURE ENABLE ALM
COMP 1 LOW PRESSURE ENABLE ALM
COMP 2 LOW PRESSURE ENABLE ALM
COMP 1 PUMPDOWN FAIL ENABLE ALM
COMP 2 PUMPDOWN FAIL ENABLE ALM
DIGI SCROLL1 HIGH TEMP ENABLE ALM
DIGI SCROLL2 HIGH TEMP ENABLE ALM
EL HEAT HIGH TEMP 5 ENABLE WRN
S247
S248
S249
S250
S251
S252
S253
S254
S255
S256
S257
S258
S259
UNIT 01