3.9.3 Analog Inputs—Liebert CW and Liebert DS Air-Cooled Units
The Liebert iCOM allows an external sensor or analog device to be connected, scaled and viewed on
the Liebert iCOM large display for Liebert CW and Liebert DS air-cooled units only. These external
devices require optional analog input connections that can be installed on new units at the factory or
added to existing units in the field. The option provides the electrical connection from the Liebert
iCOM control board to the cooling unit’s field-wiring connection area. If a Liebert CW or Liebert DS
air-cooled unit is equipped with this option, then a 0-10VDC, 0-5VDC or a 4-20mA device can be
connected to terminals 41 and 42, 43 and 44, 45 and 46 or 47 and 48. See Table 9 for analog input
availability.
Follow the settings illustrated in Figure 27 and Table 10 to set the input type based on the sensor
output being used. The default analog input is 0-5VDC. Only properly trained and qualified service
technicians should change the analog input type.
Figure 27 Analog connection control board switch
Table 9 Number of analog inputs
Unit Type Number of Analog Inputs
Liebert CW with MBV 4
Liebert CW with 3P (Stem Valve) 3; one used for valve feedback
Liebert DS Air-Cooled (DX) 2; two used for suction pressure management
NOTE
This option is not available on fluid-cooled units. Fluid-cooled units use all four analog inputs
for low and high refrigerant pressure management.
Table 10 Analog connection control board switch position
Analog Input # Input #1 Input #2 Input #3 Input #4
Control Board Switch Number 1 2 3 4 5 6 7 8
Analog Input Device Value
0 to 10VDC Off Off Off Off Off Off Off Off
0 to 5VDC On Off On Off On Off On Off
4 to 20mA On On On On On On On On
Switches #9 and #10 not applicable to Liebert CW or to Liebert DS.
On
Off
Switch Position
Switches #9 and #10 not
applicable to Liebert CW
or to Liebert DS