Emerson Liebert iCOM User Manual Page 71

  • Download
  • Add to my manuals
  • Print
  • Page
    / 108
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 70
Service Menu Parameters
65
Figure 49 Setpoints screen, page 3 of 6
Supply Sensor—Selects how the supply sensor will be used by the control. The choices are Disabled,
Cooling Only, Control and Limit. See 3.7 - Supply Control for a detailed description. The supply
sensor can only be set to Cooling Only and Control on chilled water units. The chilled water unit must
have the valve feedback if the valve type is a 3P valve (actuator). Proportional control actuators used
on motorized ball valves do not require the feedback feature.
Supply Setpoint—Sets the temperature setpoint for the supply sensor when it is set to Cooling
Only, Control or Limit.
Supply Control Type—Selects the type of control the system will use to activate cooling. A detailed
description of each control type can be found in 3.6 - Control Types.
Supply Proportional Band—Adjusts the valve’s rate of change based on the actual sensor values
deviation from setpoint when the supply sensor is set to Cooling Only or Control. The smaller this
number, the faster the valve(s) will increase cooling capacity. Too small of a number may cause the
unit to excessively reposition the valve.
Supply Integration—Adjusts the capacity of the unit based on time away from setpoint so that
accurate temperature control can be maintained. This parameter is active only when Control Type is
set to “PI.”
Supply Deadband—Prevents overshooting of the setpoint and cycling between the reheats and
cooling. The value entered into this field will be split in half by the temperature setpoint. Example: If
the temperature setpoint is 60°F (15.5°C) and a 4°F (2.2°C) deadband is set then no cooling will be
activated until 62°F (16.6°C) and no heating will be activated until 58°F (14.4°C) is reached.
Valve Pulse—Defines the minimum change in the cooling requirement before the valve will
reposition. A greater number decreases the amount of repositions and a smaller number will increase
the response of the valve.
Cooling Filter at 0% / 100%—Controls the rate of change during a valve position adjustment to
avoid overshoots. The filter value depends on the current control deviation from the setpoint. On the
setpoint (at 0%), it’s typically set lower (slow), and at the end of the P-band (at 100%), it’s typically set
higher (faster). The value is given in % control output change per second.
Return Compensation—For supply control only. Defines the maximum increase allowed to the
supply temperature setting to maintain a minimum return temperature setpoint. When the return
air temperature is above its setpoint, the supply air setpoint remains unchanged. As the return air
temperature drops below the setpoint, the supply air setpoint will be proportionally increased to
maintain the return temperature setpoint. The maximum increase is defined with the return
compensation parameter.
Page view 70
1 2 ... 66 67 68 69 70 71 72 73 74 75 76 ... 107 108

Comments to this Manuals

No comments