Service Menu Parameters
69
Figure 53 Standby settings / lead-lag screen
Number of Standby Units—Selects the number of units that will be in Standby mode. When a unit
is in standby mode, the fan will be Off and no cooling will be provided.
Rotation Frequency—Controls when a rotation will occur between the standby units and the
operating units within a network.
Rotate at (hour)—Sets the hour of the rotation
Rotate at (minute)—Sets the minute of the rotation.
Rotate by—Determines the number of positions to rotate by. Example: If there are 6 units in a
unit-to-unit network and units 1, 3 and 5 are in standby and this parameter is set to “1,” then at the
next rotation units 2, 4 and 6 will be placed in standby and units 1, 3 and 5 will become operational.
Cascade Units—Allows units to activate in Standby mode if the room temperature cannot be
maintained by the non-standby units. If “Yes” is selected, the cascade units can perform all functions
when activated from standby. This parameter can also be set for Cooling Only or Cool / Heat only.
Start all Standby Units by HT—Activates all units to cool when a High Temperature Alarm occurs.
See 3.10.1 - Calculating Next Maintenance and Diagnostics for details on these menus.