Operation
41
Fans / Heaters / Humidifier Settings and Diagnostics
Number of starts and Working hours are counted separately since the last maintenance. Total
working hours can be read in the standard working hours window (customer window).
Average Working Hours is the calculation, resulting from starts and working hours.
Starts per Day Optimum is the number of starts considered as optimum.
Starts per Day Worst is the number of starts considered as hunting (worst case).
Number of Alarms counts the alarms, happened between two service intervals.
Actual Bonus is calculated from number of starts and average working time. Can be positive
(bonus) or negative (penalty). This value influences the time remaining to the next maintenance.
Compressor 1 / 2 Settings and Diagnostics
Number of starts and Working hours are individually counted since the last maintenance. Total
working hours can be read in the standard working hours window (customer window).
Average Working Hours is the calculation, resulting from starts and working hours.
Starts per Day Optimum is the number of starts considered as optimum.
Starts per Day Worst is the number of starts considered as hunting (worst case).
Number of HP Alarms counts the high-pressure alarms, happened between 2 service intervals.
Number of LP Alarms counts the low-pressure alarms, happened between 2 service intervals.
Number of TH Alarms counts the thermal protection alarms, happened between 2 service
intervals.
Actual Bonus is calculated from number of starts and average working time. Can be positive
(bonus) or negative (penalty). This value influences the time remaining to the next maintenance.