Operation
19
The Temperature Proportional Band and Temperature Deadband parameters are in the Service
menu under the Setpoints submenu. The Temperature Setpoint parameter is in both the User Menu
and Service Menu under Setpoints.
There is a parameter AutoSet Enable (Service Menu, Setpoints), which automatically sets the
proportional bands for temperature and humidity, and both the integration time factors according to
the type of unit (chilled water, single or dual compressor).
3.2.2 Compressor Control
Depending on its type, a Liebert Precision Cooling unit may have one or two compressors with or
without unloaders or variable capacity.
Compressor Proportional Bands
One Single-Step Compressor Without Unloaders—One-Step
One single-step compressor, Cool 1, is started at 100% call for cooling from the temperature
proportional band and stopped at 0% (see Figure 13).
Figure 13 One single-step compressor without unloaders
NOTE
Before the proportional or integral setpoints can be changed, the Auto Set Enable must be
changed to NO.
Temp Setpoint: 70°F
Proportional Band: 8°F
Deadband: 2°F
75
½ Proportional Band
0%
Cooling
+ 100 %
Cooling
71 72 73 7470
½ Dead-
band
Cool 1
Off
Cool 1
On
Increasing Temperature