Emerson Liebert iCOM User Manual Page 101

  • Download
  • Add to my manuals
  • Print
  • Page
    / 108
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 100
Service Menu Parameters
95
Figure 88 Options setup, page 1 of 5
Compressor Sequence—Changes the lead compressor when cooling is activated. This parameter
can also be set to “AUTO” mode, which will activate the compressor with the lowest run hours first.
Low Pressure Alarm Delay—Sets how long the unit will ignore a low-pressure condition during
compressor startup. This parameter has previously been referred to as a Winter Start Time. This
parameter can be set between 0 to 5 minutes.
Electric Stages—Shows the number of electric stages that can be activated during a call for reheat.
This parameter is set at the factory based on the unit’s model number.
Electrical Heater Capacity (Liebert HPM only)—Shows the electrical heater capacity for units
with both electric and hot water or hot gas reheat. Reduced capacity indicates HW/HG Stage 1,
electric Stage 2; full capacity indicates HW/HG plus low capacity electric Stage 1, high capacity
electric Stage 2.
Hot Water Heat On/Off—This parameter is selectable between “Yes and No”. If “Yes” is selected the
unit is equipped with a hot water heater.
LWD Connected—This parameter is set to “Yes” if a liquid detection device is connected to the
Liebert iCOM.
Valve Control—Selects between two different methods to keep track of valve position when a
stem/3P valve is installed in the unit. This setting does not affect motorized ball valves. If “Time” is
selected then the valve position is tracked by an internal timer in the control to determine the
position or opening of the valve. If “Feedback” is selected then analog input #1 interprets the signal
from the valve to determine its position. Using the “Feedback” setting requires the setup procedure in
3.2.3 - Chilled Water Control.
3P Actuator Runtime—Sets the travel time of the valve to determine the full open and closed
position of the valve. This is set at the factory based on the valve manufacturer’s specifications.
3P Actuator Direction—Selects if the valve is a “Direct” or “Reverse” acting valve.
Page view 100
1 2 ... 96 97 98 99 100 101 102 103 104 105 106 107 108

Comments to this Manuals

No comments