Operation
32
Figure 25 Placing temperature and temperature/humidity sensors
3.7 Supply Control
3.7.1 Supply Air
The Supply Air sensor can be used to control, limit or reference the discharge air temperature of the
cooling unit. The desired supply sensor operation can be selected in the Service, Setpoints menu. The
optional supply air temperature sensor allows use of either the Supply Air control or the Supply Limit
control. This sensor can be added to existing Liebert iCOMs by purchasing the supply sensor and
wiring harness. The supply air sensor must be connected to P13 pins 1 & 2. Contact your local
Emerson representative for pricing and installation.
Supply Control: When the supply sensor is set to Control, the unit will control the amount of
cooling / heating being provided based on maintaining the discharge air temperature. The return
air sensor will still control the humidity of the room.
Supply Limit: Chilled water units may be set up with the supply air sensor to maintain a
minimum air temperature under a raised floor to help prevent condensation. In order to avoid
supply temperatures that are too low, the Supply Limit can influence the opening of three-point
or analog actuators or the output of analog valves. The control compares the deviation from the
return air setpoint and the supply limit setpoint, and calculates the output to the actuator from
the smaller deviation.
Cooling Only: When Cooling Only is selected, the cooling capacity of the system (valve or
compressor) is modulated based on the supply temperature, but allows the fan speed to be
controlled by a different sensor.
Disable: Setting the supply sensor to Disable will allow the supply sensor to be monitored but
will not affect the control output of the unit.
When the supply air sensor is set up for Supply control, additional Supply Air configuration
parameters (valve pulse, cooling filters and return compensation) can be used to further enhance
the supply air control.
NOTE
If unit is equipped with a 3P actuator type valve then the valve must be changed to utilize the
feedback signal. See 3.2.3 - Chilled Water Control.
NOTE
Supply control and limit are calculated on each unit, independent of the other sensor readings
on the network.
Temperature
Sensor
5 to 15feet
(1.5 to 4.5m)
Internal Temperature
and Humidity Sensor
Return
Air
Supply Air
Liebert Precision
Cooling Unit