Reference Manual
00809-0100-4803, Rev DA
Section 3: Configuration
April 2013
Configuration
1. Under the Differential Pressure Setup heading, edit the DP Units and Damping value as
needed.
2. The Sensor Limits and Minimum Span can be viewed under the Differential Pressure Sensor
Limits heading.
3.7.5 Static pressure
Note
For Sensor trim is a two-point sensor calibration where two end-point pressures are applied, and
all output is linearized between them. Always adjust the lower sensor trim value first to establish
the correct offset. Adjustment of the upper sensor trim value provides a slope correction to the
characterization curve based on the lower sensor trim value. The trim values allow the user to
optimize performance over a specified measuring range at the calibration temperature. see
page 4.
Figure 3-35. Variables - Static pressure tab
1. Under the Static Pressure Setup heading, edit the Absolute Pressure Units and Gage
Pressure Units as needed. The static pressure Damping may also be edited.
Mass and Energy Flow Fast Keys 1, 4, 1, 5
Direct Process Var. Output Fast Keys 1, 4, 1, 2