Emerson 3051S Specifications Page 62

  • Download
  • Add to my manuals
  • Print
  • Page
    / 188
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 61
36
Reference Manual
00809-0100-4803, Rev DA
Section 3: Configuration
April 2013
Configuration
Alarm level verification
The transmitter alarm level should be verified before returning the transmitter to service if
alarm and saturation levels are changed.
This feature is also useful in testing the reaction of the control system to a transmitter in an
alarm state. To verify the transmitter alarm values, perform a loop test and set the transmitter
output to the alarm value (see Ta bl e 3 -4, Ta bl e 3 -5, and Tab le 3 -6 on page 35, and “Analog
Output Loop Test” on page 12).
Variable saturation behavior
The analog output of the 3051S MultiVariable may respond differently based on which
measurement goes outside the sensor limits. This response will also depend on the device
configuration. Ta ble 3 -7 lists the behaviors of the analog output under different conditions.
Table 3-7. Variable saturation behavior
3.6.3 Variable mapping
The Variable Mapping tab is used to define which process variable will be mapped to each HART
variable. The primary variable represents the 4 to 20 mA analog output signal while the 2nd,
3rd, and 4th variables are digital. To edit the variable assignments, select the appropriate
process variables from the drop-down menus and click Apply.
Primary Variable Action Analog Output Behavior
Flow or Energy Flow Differential Pressure goes
outside the sensor limits
Analog output goes to high or low saturation
Flow or Energy Flow Absolute Pressure or Gage
Pressure goes outside the
sensor limits
Analog output does not saturate
Flow or Energy Flow Process Temperature goes
outside the user defined
sensor limits
Temperature Mode is Normal:
Analog output goes into high or low alarm.
Temperature Mode is Backup:
The Process Temp will go into backup mode and
be fixed at the user defined value. Analog output
will not saturate or go into alarm.
DP Differential Pressure goes
outside the sensor limits
Analog output goes to high or low saturation
AP or GP Absolute Pressure or Gage
Pressure goes outside the
sensor limits
Analog output goes to high or low saturation
Process Temp Process Temperature goes
outside the user defined
sensor limits
Direct Process Variable Output:
Analog output goes to high or low saturation
Mass and Energy Flow:
Analog output goes to high or low alarm
Mass and Energy Flow Fast Keys 1, 4, 3, 4
Direct Process Var. Output Fast Keys 1, 4, 3, 4
Page view 61
1 2 ... 57 58 59 60 61 62 63 64 65 66 67 ... 187 188

Comments to this Manuals

No comments