Reference Manual
00809-0100-4803, Rev DA
Section 3: Configuration
April 2013
Configuration
3.5 Basic device configuration
This section provides procedures for configuring the basic requirements to commission the
3051S MultiVariable Transmitter. The Basic Setup tab, shown in Figure 3-16, can be used to
perform all of the required transmitter configuration. The complete list of 475 Fast Keys for
basic setup are shown in Table 3-13 on page 69 and Table 3-14 on page 71.
Based on the configuration ordered, some measurements (i.e. static pressure, process
temperature) and/or calculation types (i.e. mass, volumetric, and energy flow) may not be
available for all fluid types. Available measurements and/or calculation types are determined by
the MultiVariable Type and Measurement Type codes ordered. See “Ordering information” on
page 27 for more information.
All screens in this section are shown for MultiVariable Type M (Fully Compensated Mass and
Energy Flow) with Measurement Type 1 (Differential Pressure, Static Pressure, and Process
Temperature). 475 Fast Keys are given for both MultiVariable Type M and P (Direct Process
Variable Output) with Measurement Type 1. 475 Fast Keys and Screens for other MultiVariable
Types and Measurement Types may vary.
Note
All screen shots in this section will be shown using AMS. Engineering Assistant screens are
similar and the instructions shown here apply to both AMS and Engineering Assistant.
When using Engineering Assistant, a Reset Page button will be shown. In Online Mode, the Reset
Page button will return all values on tab to the initial values received from the device before the
start of the configuration. If editing a previously saved configuration, the Reset Page button will
return all values on tab to those that were last saved. If starting a new configuration, all entered
values on tab will be erased.
When information is edited on any AMS tab, it will be highlighted in yellow. Edited information is
not sent to the transmitter until the Apply or OK button is clicked.
Units of measure
If a unit of measure is edited and the Apply button is clicked, the unit of measure will be changed
in the device memory and on screen, but the value may take up to 30 seconds to be updated on
the AMS screen.
Mass and Energy Flow Fast Keys 1, 3
Direct Process Var. Output Fast Keys 1, 3