Reference Manual
00809-0100-4803, Rev DA
Section 3: Configuration
April 2013
Configuration
Note
To be in compliance with appropriate national or international standards, beta ratios and
differential producer diameters should be within the limits as listed in the applicable standards.
The Engineering Assistant software will alert the user if a primary element value exceeds these
limits, but will allow the user to proceed with the flow configuration.
3.4.8 Save / send
The Save / Send Configuration tab shown in Figure 3-11 allows the user to view, save, and send
the configuration information to the 3051S MultiVariable Transmitter with the Fully
Compensated Mass and Energy Flow Feature Board.
1. Review the information under the Flow Configuration heading and Device
Configuration heading.
Note
For more information on device configuration, see “Basic device configuration” on page 31.
Figure 3-11. Save / send configuration tab (offline mode)
2. Click on the icon above each window to be taken to the appropriate screen to edit the
configuration information. To return to the
Save / Send tab, click Save / Send in the left menu.
3. When all information is correct, see “Sending a configuration in offline mode” on
page 24 or “Sending a configuration in online mode” on page 25.