Section 2: Installation
April 2013
Installation
3. Close the equalize valve on
the high pressure (upstream)
side.
Test
(Plugged)
Test
(Plugged)
Equalize
(closed)
Process
Isolate
(closed)
Isolate
(open)
H
L
Process
Equalize
(closed)
Drain Vent
(closed)
4. Finally, to return the
transmitter to service, open
the low side isolation valve.
Test
(Plugged)
Test
(Plugged)
Equalize
(closed)
Process
Isolate
(open)
Isolate
(open)
H
L
Process
Equalize
(closed)
Drain Vent
(closed)