Infrastructure Management & MonitoringFor Business-Critical Continuity™Liebert® Universal Monitor™User Manual
IntroductionLiebert® Universal Monitor™21.5 Outside Enclosure OverviewThe enclosure for the Liebert Universal Monitor controller board comes in two si
View Status MenusLiebert® Universal Monitor™92A.4 VIEW STATUS MENUS The View Status menu allows any user to view currently active alarms, monitoring d
View Status Menus93 Liebert® Universal Monitor™A.4.1 View Active Alarms For details on this feature, see 7.1 - View Active Alarms. View Active AlarmsA
View Status MenusLiebert® Universal Monitor™94A.4.2 View Alarm LogFor details on this feature, see 7.2 - View Alarm Log.View Alarm LogALARM LOGAlarm h
View Status Menus95 Liebert® Universal Monitor™A.4.3 View Event LogFor details on this feature, see 7.3 - View Event Log.View Event LogEVENT LOGEvent
View Status MenusLiebert® Universal Monitor™96A.4.4 View Trend LogFor details on this feature, see 7.4 - View Trend Log.View Trend LogTREND LOGTrend h
View Status Menus97 Liebert® Universal Monitor™A.4.5 View Input StatusFor details on this feature, see 7.5 - View Input Status.View Input & Sensor
View Status MenusLiebert® Universal Monitor™98A.4.6 View Output StatusFor details on this feature, see 7.6 - View Output Status.View Output StatusOUTP
View Status Menus99 Liebert® Universal Monitor™A.4.7 View Pager NumbersFor details on this feature, see 7.7 - View Pager Numbers.View Pager NumbersPAG
Silence Alarm & Back Up Log Files (Service Terminal Interface only)Liebert® Universal Monitor™100A.5 SILENCE ALARM & BACK UP LOG FILES (SERVIC
Silence Alarm & Back Up Log Files (Service Terminal Interface only)101 Liebert® Universal Monitor™A.5.2 Back Up Log Files (Service Terminal Interf
Introduction3Liebert® Universal Monitor™1.6 Typical ConfigurationFigure 3 shows an example of external devices connected to the Liebert Universal Moni
Silence Alarm & Back Up Log Files (Service Terminal Interface only)Liebert® Universal Monitor™102Back Up Event Log FileBackup Log Files - Event Lo
Silence Alarm & Back Up Log Files (Service Terminal Interface only)103 Liebert® Universal Monitor™Back Up Trend Log FilesBackup Log Files - Trend
Setup MenuLiebert® Universal Monitor™104A.6 SETUP MENUThe Setup menu allows the user to configure the Universal Monitor—setting up inputs and outputs
Setup Menu105 Liebert® Universal Monitor™Setup Menu This section presents Service Terminal Interface screens for each of the following:* Setup System
Setup MenuLiebert® Universal Monitor™106A.6.1 Setup InputFor details on this feature, see 9.3 - Setup System - Setup Input.Setup Input - Main Board In
Setup Menu107 Liebert® Universal Monitor™Setup Input -Expansion Board InputsSETUP INPUTSetup for discreteinput pointsSelect input to editINPUT DEFI
Setup MenuLiebert® Universal Monitor™108A.6.2 Setup Common AlarmFor details on this feature, see 9.4 - Setup System - Setup Common Alarm.Setup Common
Setup Menu109 Liebert® Universal Monitor™A.6.3 Setup SensorFor details on this feature, see 9.5 - Setup System - Setup Sensor.Setup SensorSETUP SENSOR
Setup MenuLiebert® Universal Monitor™110>[>COMMAND SUCCESSFUL>CHANGE OFFSET VALUE.>[000.0]>[>COMMAND SUCCESSFUL>IS SENSOR AN ALAR
Setup Menu111 Liebert® Universal Monitor™A.6.4 Setup I/O MatrixFor details on this feature, see 9.6 - Setup System - Setup I/O Matrix.Setup I-O Matrix
IntroductionLiebert® Universal Monitor™41.7 Controller Board OverviewThe Liebert Universal Monitor controller board has connectors for eight digital i
Setup MenuLiebert® Universal Monitor™112>[>COMMAND SUCCESSFUL>MAP INPUT_01 TO OUTPUT06-YES(Y) OR NO(N)?>[N]>[>COMMAND SUCCESSFUL>
Setup Menu113 Liebert® Universal Monitor™Setup I-O Matrix - Map Input to Output - Expansion Board InputsSETUP I/O MATRIXProgram inputs & sensorsto
Setup MenuLiebert® Universal Monitor™114>MAP INPUT_09 TO OUTPUT01-YES(Y) OR NO(N)?>[Y]>[>COMMAND SUCCESSFUL>MAP INPUT_09 TO OUTPUT02-YE
Setup Menu115 Liebert® Universal Monitor™Setup I-O Matrix - Map Sensor to OutputSETUP I/O MATRIXProgram inputs & sensorsto control outputsSelect t
Setup MenuLiebert® Universal Monitor™116>[>COMMAND SUCCESSFUL>MAP SENSOR_1 HIGH STPT TO OUTPUT06-YES(Y) OR NO(N)?>[N]>[>COMMAND SUCC
Setup Menu117 Liebert® Universal Monitor™A.6.5 Setup OutputFor details on this feature, see 9.7 - Setup System - Setup Output.Setup Output - Main Boar
Setup MenuLiebert® Universal Monitor™118Setup Output - Expansion Board OutputsSETUP OUTPUTSetup for discreteoutput pointsSelect output to editOUTPUT
Setup Menu119 Liebert® Universal Monitor™A.6.6 Setup Modem & PagersFor details on this topic, see 9.8 - Setup System - Setup Modem & Pagers.Pa
Setup MenuLiebert® Universal Monitor™120Modem SetupFor details on this feature, see 9.8.1 - Modem Setup - Initialization String and 9.8.2 - Modem Setu
Setup Menu121 Liebert® Universal Monitor™A.6.7 Setup System InfoThis section presents Service Terminal Interface screens for choices 1 through 9 in th
Introduction5Liebert® Universal Monitor™J - Status LEDs Indicates the operational status of the controller board. 1.9: LED IndicatorsK - Digital outpu
Setup MenuLiebert® Universal Monitor™122Change Date & Time/Automatic Daylight Saving TimeFor details on this feature, see 9.9.2 - Change Date &
Setup Menu123 Liebert® Universal Monitor™Connect Battery For details on this feature, see 9.9.4 - Connect Battery.Backup and Upload Configuration File
Setup MenuLiebert® Universal Monitor™124Setup Service Phone Number For details on this feature, see 9.9.6 - Setup Serv Ph Num - Enter Phone Number and
Setup Menu125 Liebert® Universal Monitor™Factory Defaults For details on this feature, see 9.9.8 - Factory Defaults.Firmware Update (Service Terminal
Setup MenuLiebert® Universal Monitor™126Initiate Remote Alarm Test (Service Terminal Interface only)For details on this feature, see 9.9.10 - Initiate
Setup Menu127 Liebert® Universal Monitor™A.6.8 Connect Expansion BoardFor details on this feature, see 9.10 - Setup Exp Board - Optional Expansion Boa
Setup MenuLiebert® Universal Monitor™128A.6.9 Override Output For details on this feature, see 9.11 - Manual Output Ctrl.Override Output - Main Board
Setup Menu129 Liebert® Universal Monitor™Override Output - Expansion Board OutputsOVERRIDE OUTPUTManually overridean output pointSelect output to over
Setup MenuLiebert® Universal Monitor™130A.6.10 Clear Alarms & LogsFor details on this topic, see 9.12 - Clear Alarms & Logs.Clear Active Alarm
Setup Menu131 Liebert® Universal Monitor™Clear the Event Log For details on this feature, see 9.12.3 - Clear the Event Log.Clear the Trend LogsFor det
IntroductionLiebert® Universal Monitor™61.8 Optional Expansion Board OverviewThe Liebert Universal Monitor Expansion Board, purchased separately, has
Setup MenuLiebert® Universal Monitor™132APPENDIX B- DEFAULT SETTINGS QUICK REFERENCE GUIDEThis appendix provides a quick reference to default settings
Setup Menu133 Liebert® Universal Monitor™Table 38 Universal Monitor - other default settingsJUMPER SETTINGSFeature Default Other OptionsDigital output
Setup MenuLiebert® Universal Monitor™134Table 39 Expansion Board - default settings for inputs and outputsDEFAULT SETTINGS - DIGITAL INPUTS (FROM TABL
Ensuring The High AvailabilityOf Mission-Critical Data And Applications.Emerson Network Power, a business of Emerson (NYSE:EMR),is the global leader i
Introduction7Liebert® Universal Monitor™1.9 LED IndicatorsThe Liebert Universal Monitor controller board has LED indicators that show the status of in
IntroductionLiebert® Universal Monitor™81.10 LED Indicators - Optional Expansion BoardThe optional Expansion Board, purchased separately, has LED indi
Introduction9Liebert® Universal Monitor™1.11 Typical SequenceFigure 4 shows a typical sequence of how the Liebert Universal Monitor functions after de
Installation - Main BoardLiebert® Universal Monitor™102.0 INSTALLATION - MAIN BOARDThis section provides instructions for installing, mounting and con
Installation - Main Board11 Liebert® Universal Monitor™2.2 Surface-Mounting the Liebert Universal MonitorAfter determining where to place the unit, ch
Installation - Main BoardLiebert® Universal Monitor™122.3 Flush-Mounting the Liebert Universal MonitorThe Liebert Universal Monitor may be flush-mount
Installation - Main Board13 Liebert® Universal Monitor™2.4 Connect Power to the Liebert Universal MonitorThe Liebert Universal Monitor requires 24VAC
Installation - Main BoardLiebert® Universal Monitor™142.4.2 Termination and Mounting - Large EnclosureInput Power ConnectionsTo connect electrical pow
Installation - Main Board15 Liebert® Universal Monitor™Troubleshooting - Transformer ModuleA common problem and possible solution are shown in the tab
Installation - Optional Expansion BoardLiebert® Universal Monitor™163.0 INSTALLATION - OPTIONAL EXPANSION BOARDThis section provides instructions for
Installation - Optional Expansion Board17 Liebert® Universal Monitor™3.2 Surface-Mounting the Optional Expansion BoardAfter determining where to place
Installation - Optional Expansion BoardLiebert® Universal Monitor™183.3 Flush-Mounting the Optional Expansion BoardThe optional Expansion Board may be
Installation - Optional Expansion Board19 Liebert® Universal Monitor™3.4 Input Power Connections - Optional Expansion BoardThe optional Expansion Boar
Wiring and Connections - Main BoardLiebert® Universal Monitor™204.0 WIRING AND CONNECTIONS - MAIN BOARD4.1 Wiring SpecificationsInput and output conne
Wiring and Connections - Main Board21 Liebert® Universal Monitor™4.2 Connecting Digital Inputs and Digital OutputsThe digital inputs and digital outpu
iTABLE OF CONTENTS1.0 INTRODUCTION1.1 Methods of Viewing and Configuring the Liebert Universal Monitor. . . . . . . . . . . . . . . . . . . 11.2 Data
Wiring and Connections - Main BoardLiebert® Universal Monitor™224.2.3 Setting the Digital Output JumpersEach digital output has an associated jumper t
Wiring and Connections - Main Board23 Liebert® Universal Monitor™4.3.1 Setting the 12VDC/24VDC Analog Power JumperThe analog power jumper sets the com
Wiring and Connections - Main BoardLiebert® Universal Monitor™244.4 Connecting Common Alarm OutputsThe common alarm relay, found in the top right corn
Wiring and Connections - Optional Expansion Board25 Liebert® Universal Monitor™5.0 WIRING AND CONNECTIONS - OPTIONAL EXPANSION BOARD5.1 Wiring Specifi
Wiring and Connections - Optional Expansion BoardLiebert® Universal Monitor™265.2 Connecting Inputs and OutputsThe Liebert Universal Monitor optional
Wiring and Connections - Optional Expansion Board27 Liebert® Universal Monitor™5.2.2 Connecting Digital OutputsThe eight digital outputs are found at
Wiring and Connections - Optional Expansion BoardLiebert® Universal Monitor™285.2.3 Setting the Digital Output DIP SwitchesEach digital output on the
Wiring and Connections - Optional Expansion Board29 Liebert® Universal Monitor™5.3 Connect to the Liebert Universal MonitorTwo steps are required to e
Overview of MenusLiebert® Universal Monitor™306.0 OVERVIEW OF MENUSThere are two ways to access the Liebert Universal Monitor: the LCD on the front of
Overview of Menus31 Liebert® Universal Monitor™6.1 Opening Screen OverviewThe Liebert Universal Monitor displays the Opening Screen at startup, as sho
ii5.0 WIRING AND CONNECTIONS - OPTIONAL EXPANSION BOARD5.1 Wiring Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
View Status OptionsLiebert® Universal Monitor™327.0 VIEW STATUS OPTIONSThe View Status menu allows any user to view currently active alarms, monitorin
View Status Options33 Liebert® Universal Monitor™7.1 View Active AlarmsThe Active Alarm screen displays all alarms that are occurring, up to a maximum
View Status OptionsLiebert® Universal Monitor™347.2 View Alarm LogThe Alarm Log contains up to 99 records of alarms that have occurred. Records are ad
View Status Options35 Liebert® Universal Monitor™7.3 View Event LogIn addition to alarms, the Liebert Universal Monitor tracks other changes in the Ev
View Status OptionsLiebert® Universal Monitor™367.4 View Trend LogThe Liebert Universal Monitor takes readings of configured analog input sensors at r
View Status Options37 Liebert® Universal Monitor™7.5 View Input StatusThe Input Status option allows you to view the current status of all inputs: the
View Status OptionsLiebert® Universal Monitor™387.6 View Output StatusThe Output Status option allows you to view the current status of all eight outp
View Status Options39 Liebert® Universal Monitor™7.7 View Pager NumbersThe Liebert Universal Monitor may be set up to dial pager numbers when an alarm
Silence Alarm & Backup Log Files (Service Terminal Interface)Liebert® Universal Monitor™408.0 SILENCE ALARM & BACKUP LOG FILES (SERVICE TERMIN
Silence Alarm & Backup Log Files (Service Terminal Interface)41 Liebert® Universal Monitor™8.2 Back Up Log Files (Service Terminal Interface only)
iii9.5 Setup System - Setup Sensor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 499.5.1 Identif
Silence Alarm & Backup Log Files (Service Terminal Interface)Liebert® Universal Monitor™425. At the top of the HyperTerminal window, shown below,
System and Control Options43 Liebert® Universal Monitor™9.0 SYSTEM AND CONTROL OPTIONSThe System and Control menu allows you to configure the Liebert
System and Control OptionsLiebert® Universal Monitor™44Figure 14 shows the main options available from the System & Control menu.Figure 14 Menu ov
System and Control Options45 Liebert® Universal Monitor™9.2 Setup System - OverviewThe Setup System screen displays seven options that allow you to co
System and Control OptionsLiebert® Universal Monitor™469.3.1 Change Label (Name of Input)Each input has a default label (Input_01, Input_02, etc.) tha
System and Control Options47 Liebert® Universal Monitor™9.3.4 Set Up Alarmable Inputs in Latched or Unlatched ModeAlarmable input points may be set up
System and Control OptionsLiebert® Universal Monitor™489.4 Setup System - Setup Common AlarmThe audible alarm sounds after the Liebert Universal Monit
System and Control Options49 Liebert® Universal Monitor™9.5 Setup System - Setup SensorThe Liebert Universal Monitor has four analog sensor input poin
System and Control OptionsLiebert® Universal Monitor™509.5.1 Identify the Sensor as ConnectedTo make use of an analog sensor, you must specify it as C
System and Control Options51 Liebert® Universal Monitor™9.5.4 Change 4 mA ValueFor the 4 mA value, enter the smallest value for the range of the senso
ivAPPENDIX A-SERVICE TERMINAL INTERFACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .85A.1 Comparison of Functions: LC
System and Control OptionsLiebert® Universal Monitor™529.5.7 Define Sensor as Alarmable or EventEach sensor may be defined as Alarmable (AL) or as an
System and Control Options53 Liebert® Universal Monitor™9.5.9 Change Low SetpointThe Low Setpoint value is typically above the 4 mA value for the sens
System and Control OptionsLiebert® Universal Monitor™549.5.11 Set Up Delay TimeEach sensor may be set up with a specified time delay between the trigg
System and Control Options55 Liebert® Universal Monitor™9.6 Setup System - Setup I/O MatrixThe Setup I/O Matrix menu allows you to configure the Liebe
System and Control OptionsLiebert® Universal Monitor™56Map Input to Expansion Board Output• From the Select Outputs menu, select Map to Exp Board if y
System and Control Options57 Liebert® Universal Monitor™9.6.2 Set Up Mapping for an Analog Sensor Input• Use the arrows ↑↓ to choose Map Sensor To Out
System and Control OptionsLiebert® Universal Monitor™589.7 Setup System - Setup OutputThe Liebert Universal Monitor has eight outputs that may be conf
System and Control Options59 Liebert® Universal Monitor™9.7.3 Set Expansion Board Output by DIP SwitchIf you choose Change State from the Setup Output
System and Control OptionsLiebert® Universal Monitor™609.8 Setup System - Setup Modem & PagersTo use the modem and pager features, be sure to conn
System and Control Options61 Liebert® Universal Monitor™Select Modem Setup4. From the Setup System Menu, shown at right, use the arrows↑↓ to choose Se
vFIGURESFigure 1 Small enclosure—external features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System and Control OptionsLiebert® Universal Monitor™629.8.2 Modem Setup - Additional Features (Service Terminal Interface only)The Service Terminal I
System and Control Options63 Liebert® Universal Monitor™Enable Modem Diagnostic MessagesEnabling modem diagnostics will provide the following addition
System and Control OptionsLiebert® Universal Monitor™649.8.3 Pager Setup - Pager Number and PINThe Liebert Universal Monitor may be configured to dial
System and Control Options65 Liebert® Universal Monitor™Enter a Pager Number• From the Setup Pager Menu, choose Setup Pager Number for the selected pa
System and Control OptionsLiebert® Universal Monitor™669.8.4 Pager Setup - Communications Check (Service Terminal Interface only)The Service Terminal
System and Control Options67 Liebert® Universal Monitor™Enable Communications CheckEnabling this function permits a daily communications test between
System and Control OptionsLiebert® Universal Monitor™689.9 Setup System - Setup System InfoThe Setup System Info options allow users to:• Change Passw
System and Control Options69 Liebert® Universal Monitor™9.9.1 Change PasswordA password is required to access the Liebert Universal Monitor system and
System and Control OptionsLiebert® Universal Monitor™709.9.3 Setup Site IDYou may enter a Site ID to identify the Liebert Universal Monitor’s location
System and Control Options71 Liebert® Universal Monitor™9.9.5 Backup and Upload Configuration File (Service Terminal Interface only)This operation may
viTable 32 Service phone number dialing results . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74Table
System and Control OptionsLiebert® Universal Monitor™72Back Up the Configuration File8. At the prompt to Initiate a Backup of Configuration File, ente
System and Control Options73 Liebert® Universal Monitor™Upload the Configuration File13. At the prompt to Initiate an Upload of Configuration File, en
System and Control OptionsLiebert® Universal Monitor™749.9.6 Setup Serv Ph Num - Enter Phone NumberThe Service Phone Number (Serv Ph Num) is used for
System and Control Options75 Liebert® Universal Monitor™9.9.7 Setup Serv Ph Num - Communications Check (Service Terminal Interface only)The Service Te
System and Control OptionsLiebert® Universal Monitor™769.9.8 Factory DefaultsAt any time, you may restore all default values for settings in the Liebe
System and Control Options77 Liebert® Universal Monitor™2. The firmware update is a two-step process—this step describes how to upload the file prog##
System and Control OptionsLiebert® Universal Monitor™789.9.10 Initiate Remote Alarm Test (Service Terminal Interface only)The service phone number is
System and Control Options79 Liebert® Universal Monitor™If the test is NOT successful, check the following:• Modem configuration (see 9.8.1 - Modem Se
System and Control OptionsLiebert® Universal Monitor™809.11 Manual Output CtrlThe Manual Output Ctrl feature allows you to manually change the state o
System and Control Options81 Liebert® Universal Monitor™9.12 Clear Alarms & LogsThe Clear Alarms & Logs menu allows you to clear active alarms
Introduction1Liebert® Universal Monitor™1.0 INTRODUCTIONExtensive capabilities can put the Liebert Universal Monitor at the heart of your protective n
System and Control OptionsLiebert® Universal Monitor™829.12.3 Clear the Event LogThe event log contains up to 99 records of events detected by the Lie
Specifications83 Liebert® Universal Monitor™10.0 SPECIFICATIONS10.1 Liebert Universal Monitor SpecificationsPowerRequirementsSmall Enclosure Large Enc
SpecificationsLiebert® Universal Monitor™8410.2 Optional Expansion Board SpecificationsPowerRequirementsUMEXPNOTE24VAC ±10% of nominal;50/60 Hz, 0.6A,
Comparison of Functions: LCD and Service Terminal Interface85 Liebert® Universal Monitor™APPENDIX A- SERVICE TERMINAL INTERFACEThe Service Terminal In
Connecting to the Service Terminal InterfaceLiebert® Universal Monitor™86A.2 CONNECTING TO THE SERVICE TERMINAL INTERFACEThis section describes how to
Connecting to the Service Terminal Interface87 Liebert® Universal Monitor™A.2.2 Create a ConnectionBefore connecting to the Service Terminal Interface
Connecting to the Service Terminal InterfaceLiebert® Universal Monitor™88A.2.3 Set Up the COM1 Port - Direct Connection OnlyThe following steps apply
Connecting to the Service Terminal Interface89 Liebert® Universal Monitor™A.2.4 Set Up the Connection’s PropertiesThe following steps are needed for b
Connecting to the Service Terminal InterfaceLiebert® Universal Monitor™90A.2.5 Connect to the Service Terminal InterfaceAfter creating and setting up
Overview of Menus91 Liebert® Universal Monitor™A.3 OVERVIEW OF MENUSThe Main Menu offers choices for viewing the status of the Universal Monitor, sile