Wiring and Connections - Optional Expansion Board
29 Liebert
®
Universal Monitor
5.3 Connect to the Liebert Universal Monitor
Two steps are required to establish connection between the optional Expansion Board and the Liebert
Universal Monitor.
5.3.1 Connect EIA485 Connectors to Main Board
To connect the optional Expansion Board to the Liebert Universal Monitor:
1. Turn OFF electrical power to the Liebert Universal Monitor and disconnect power from the
Expansion Board.
2. If necessary, remove a conduit knockout to permit wire entry into each enclosure.
3. Bring the wire(s) into each enclosure through a conduit knockout or access slot.
4. Loosen the appropriate screw and slip the stripped end of the wire into the terminal block,
connecting the cables as shown in the figure below):
Connect the Liebert Universal Monitor 485 connector UM- to Expansion Board connector
EIA485+.
Connect the Liebert Universal Monitor 485 connector UM+ to Expansion Board connector
EIA485-.
5. Tighten each screw until it holds the wire snugly.
5.3.2 Enable the Connection via Firmware
After making the cable connections described in the previous section, you must specify the Expansion
Board as connected using either the LCD or Service Terminal Interface.
For instructions, refer to the appropriate section:
LCD interface (see 9.10 - Setup Exp Board - Optional Expansion Board)
Service Terminal Interface (see A.6.8 - Connect Expansion Board)