AC PowerFor Business-Critical Continuity™Liebert® NXL™Installation Manual – 500-750kVA, 0.9PF, 60Hz, Three-Phase, Single-Module & Multi-Module

Page 2 - Product Warranty Registration

Mechanical Installation41.3.2 StorageShould the equipment not be installed immediately, it must be stored in a room for protection against excessive h

Page 3 - TABLE OF CONTENTS

Mechanical Installation51.4.4 Kick Plate InstallationKick plates must be installed. If the unit is to be installed in a position that does not permit

Page 4

Mechanical Installation61.6 Cable EntryCables can enter the UPS cabinet from bottom or top into the Input/Output (I/O) section of the unit; see the fi

Page 5

UPS Electrical Installation72.0 UPS ELECTRICAL INSTALLATIONThis chapter provides guidelines for qualified installers who must have knowledge of local

Page 6

UPS Electrical Installation82.3 Sizing the Input Breaker feeding a Liebert NXL UPSThe rectifier nominal input current value (Table 10) is based on pro

Page 7 - SAVE THESE INSTRUCTIONS

UPS Electrical Installation95. For control connection details, see 2.4 - Control Cable and Communication.6. Close and secure the interior and exterior

Page 8

UPS Electrical Installation102.4 Control Cable and CommunicationBased on your site’s specific needs, the UPS may require auxiliary connections to mana

Page 9 - 1.0 MECHANICAL INSTALLATION

UPS Electrical Installation11Table 2 UPS control contacts with battery cabinet or module battery disconnectItemTerminalBlock PinConnects to(Descriptio

Page 10 - 1.4 Positioning

UPS Electrical Installation122.4.2 Multi-Module CommunicationParalleling cables that connect the module to the system are connected to terminals P3101

Page 11 - 1.5 System Composition

UPS Electrical Installation132.4.3 Remote Input Breaker (RIB)For systems that use Remote Input Breakers (RIB), the controls for the Aux contacts, UVR,

Page 12 - 1.6 Cable Entry

CONTACTING EMERSON NETWORK POWER FOR SUPPORTTo contact Emerson Network Power Liebert Services for information or repair service in the United States,

Page 13 - 2.2 Power Cables

UPS Electrical Installation14RIB must be Listed UL 489 (Molded Case Circuit Breaker) or UL 1066 (Low Voltage AC Power Circuit Breaker) that are requir

Page 14 - UPS Electrical Installation

UPS Electrical Installation15Figure 8 Remote Output Breaker diagramSee Table 11 for required current ratings.Table 7 Remote IOB contacts from remote b

Page 15 - Detail A

UPS Electrical Installation162.5 Digital LBSThe Load Bus Sync interface enables independent UPS units to remain in sync when operating on battery or w

Page 16 - 2.4.1 Dry Contacts

UPS Electrical Installation172.6 Configuring Neutral and Ground ConnectionsImproper grounding is the largest single cause of UPS installation and star

Page 17

UPS Electrical Installation182.6.4 Multi-Module SystemsFor both N+1 and 1+N systems, the neutrals of all UPS modules in the system must be connected t

Page 18 - Communication Board in system

UPS Electrical Installation19Figure 12 Grounding diagram, three-wire multi-module systemSwitchgearUPS #1SourceGNNGUPS #2NGUPS #3NGTo connect equipment

Page 19

UPS Electrical Installation20Figure 13 Grounding diagram, four-wire multi-module systemSwitchgearUPS #1SourceGNBPSSNGUPS #2BPSSNGUPS #3BPSSNGTo connec

Page 20

Optional Equipment213.0 OPTIONAL EQUIPMENT3.1 Single-Module System Options3.1.1 Matching Maintenance Bypass CabinetA matching Liebert NXL Maintenance

Page 21 - Connections

Installation Drawings224.0 INSTALLATION DRAWINGSFigure 14 Main components, 500kVA Liebert NXL SMS and 1+N multi-module unit with static bypassOption B

Page 22 - 2.5 Digital LBS

Installation Drawings23Figure 15 Outline drawing, Liebert NXL 500kVA UPS SMS and 1+N multi-module unit with static bypassInverter Split (Part B)LEFT S

Page 23

iTABLE OF CONTENTSIMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11.0 ME

Page 24 - 2.6.4 Multi-Module Systems

Installation Drawings24Figure 16 Input terminal details, Liebert NXL 500kVA UPS, SMS and 1+N multi-module unit with static bypassNOTES1. All dimension

Page 25 - Grounding for 1+N

Installation Drawings25Figure 17 Output terminal details, Liebert NXL 500kVA UPS, SMS and 1+N multi-module unit with static bypassNOTES:1.All dimensio

Page 26

Installation Drawings26Figure 18 Base drawing, Liebert NXL 500kVA UPS, SMS and 1+N multi-module unit with static bypass BRACKET MOUNTING LOCATIONS(M1

Page 27 - 3.0 OPTIONAL EQUIPMENT

Installation Drawings27Figure 19 Field connections, shipping split 500kVA Liebert NXL, multi-module or SMS with static bypass, Page 1WH P/NSTART(Part

Page 28 - 4.0 INSTALLATION DRAWINGS

Installation Drawings28Figure 20 Field connections, shipping split 500kVA Liebert NXL, multi-module or SMS with static bypass, Page 2DC POWER CONNECTI

Page 29 - Installation Drawings

Installation Drawings29WH P/NSTART(Part A- Rectifier Cabinet)FINISH(Part B- Inverter Cabinet) LABEL604308G1 UPSC02-806705Bypass Control BoardTO: 02-80

Page 30

Installation Drawings30Figure 21 Main components, 625/750kVA Liebert NXL, N+1 multi-module unit without static bypassLiebertIntelliSlotHousingsHMI Scr

Page 31 - RIGHT SIDE (PART B)

Installation Drawings31Figure 22 Main components, 625/750kVA Liebert NXL UPS, SMS and 1+N multi-module unit with static bypassOPTION BOX(6 SLOTS)LIEBE

Page 32

Installation Drawings32Figure 23 Outline drawing, 625/750kVA Liebert NXL, N+1 multi-module unit without static bypassNOTES1. All dimensions are in inc

Page 33 - PART B - WIRE FINISHING POINT

Installation Drawings33Figure 24 Outline Drawing, 625/750kVA Liebert NXL, SMS and 1+N multi-module unit with static bypassNOTES1. All dimensions are i

Page 34 - PART B - WIRE STARTING POINT

ii4.0 INSTALLATION DRAWINGS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .225.0 SPECIFICATIONS . . .

Page 35

Installation Drawings34Figure 25 Base detail drawing, 625/750kVA Liebert NXL, N+1 multi-module unit without static bypassBracket Mounting Locations (M

Page 36 - DOORS AND INNER SKINS REMOVED

Installation Drawings35Figure 26 Base Drawing, 625/750kVA Liebert NXL, SMS and 1+N multi-module unit with static bypassBRACKET MOUNTING LOCATIONS(M10

Page 37

Installation Drawings36Figure 27 Input terminal detail, 625/750kVA Liebert NXL, N+1 multi-module unit without static bypassNotes1. All dimensions are

Page 38

Installation Drawings37Figure 28 Input terminal detail, 625/750kVA Liebert NXL, SMS and 1+N multi-module unit with static bypassNOTES:1. ALL DIMENSION

Page 39

Installation Drawings38Figure 29 Output terminal detail, 625/750kVA Liebert NXL, N+1 multi-module unit without static bypass (continued)NOTES:1. All d

Page 40 - Bottom Cable Entry Panels

Installation Drawings39Figure 30 Output terminal detail, 625/750kVA Liebert NXL, SMS and 1+N multi-module unit with static bypass, continuedNOTES:1. A

Page 41 - PILLARS REMOVED FOR CLARITY

Installation Drawings40Figure 31 Shipping split 625/750kVA Liebert NXL without static bypass(+) DC Busbar(-) DC BusbarM10 Flat WasherM10 Ribbed Washer

Page 42 - Input Ground

Installation Drawings41WH P/NSTART (Part A - Rectifier Cabinet)FINISH(Part B - Inverter Cabinet) LABEL531985G1 UPSC (Control Door) 02-806704 - Inverte

Page 43 - LEFT SIDE (PART A)

Installation Drawings42Figure 32 Shipping split 625/750kVA Liebert NXL without static bypass (continued)02-806708-Low Voltage Wire Connections Between

Page 44 - RIGHT FRONT

Installation Drawings43WH P/NSTART(Part B - Inverter Cabinet)FINISH(Part A - Rectifier Cabinet) LABEL532049G1 02-806716- AC Distribution Board 02-8067

Page 45

iiiFigure 33 Shipping Split, 625/750kVA Liebert NXL, SMS and 1+N multi-module unit with static bypass . . . . . . . . . . . . . . . . . . . . . . . .

Page 46

Installation Drawings44Figure 33 Shipping Split, 625/750kVA Liebert NXL, SMS and 1+N multi-module unit with static bypassPART A - WIRE STARTING POIN

Page 47

Installation Drawings45WH P/NSTART(Part A - Rectifier Cabinet)FINISH(Part B - Inverter Cabinet) LABEL531985G1 UPSC (Control Door) 02-806704-Inverter G

Page 48

Installation Drawings46Figure 34 Shipping Split, 625/750kVA Liebert NXL, SMS and 1+N multi-module unit with static bypass, continuedLow Voltage Wire C

Page 49

Installation Drawings47WH P/NStart(Part B - Inverter Cabinet)Finish(Part A - Rectifier Cabinet) Label532049G1 02-806716-AC Distribution Board 02-80671

Page 50 - DETAIL A

Installation Drawings48Figure 35 Single-input wire cabinetM6 hardware for Ground Plateprovided in shipped-loose baginside Wire CabinetRemove Side Pane

Page 51

Specifications495.0 SPECIFICATIONSTable 9 Liebert NXL UPS specificationsModel Size 500kVA 625kVA 750kVAInput ParametersInput Voltage to Rectifier, VA

Page 52

Specifications50 Physical Parameters and Standards, in (mm) Width, With Static Bypass 111.6 (2835) 140.5 (3568)Width, without Static Bypass 111.6 (283

Page 53

Specifications51Notes on Tables1. Nominal input current (considered continuous) is based on full-rated output load. Maximum current includes nominal i

Page 54

Specifications52Table 14 Recommended conduit and cable sizesRectifier InputUPS Rating Voltage(VAC)Nominal Selection(#) Conduit Size, Ph, GkVA kW500 45

Page 55 - 5.0 SPECIFICATIONS

Specifications53Figure 36 Inverter overload dataTime, secondsLoad, PercentTime, secondsContinuous1363604025151064210.510015925039460093750003748

Page 57 - Notes on Tables

Specifications54Figure 37 Bypass overload data1000500150010002000300040005000250035004500110110% Load - 15,000 SecondsLoad, PercentTime, SecondsTime,

Page 58

Specifications55Table 15 Recommended lug sizesCable SizeT&B Series 54000One HoleT&B Series 54000Two Hole#8 AWG 54930BE 54850BE#6 AWG 54905BE 2

Page 59 - Continuous

Specifications56NOTES

Page 61

Ensuring The High AvailabilityOf Mission-Critical Data And Applications.Emerson Network Power, a business of Emerson (NYSE:EMR),is the global leader i

Page 62

1IMPORTANT SAFETY INSTRUCTIONSSAVE THESE INSTRUCTIONSThis manual contains important instructions that should be followed during installation of your L

Page 63

2NOTICEThis unit complies with the limits for a Class A digital device, pursuant to Part 15 Subpart J of the FCC rules. These limits provide reasonabl

Page 64 - SL-25434_REV9_11-11

Mechanical Installation31.0 MECHANICAL INSTALLATION1.1 IntroductionThis section describes the requirements that must be taken into account when planni