Liebert® NXL™Operation and Maintenance Manual–250-1100kVA, 60Hz, Three Phase Single-Module & Multi-Module

Page 2 - BATTERY CABINET PRECAUTIONS

IntroductionLiebert® NXL™21.0 INTRODUCTION1.1 General DescriptionThe Liebert NXL UPS provides continuous, high-quality AC power to your business-criti

Page 3 - TABLE OF CONTENTS

UPS Alarm and Status MessagesLiebert® NXL™92Low BattCapacityOne or more battery circuit breakers are open.This alarm applies if the system includes mo

Page 4

UPS Alarm and Status Messages93 Liebert® NXL™MainControlFaultThe UPS has transferred to Bypass due to a loss of communications with the Main Controlle

Page 5

UPS Alarm and Status MessagesLiebert® NXL™94ManualXferInhibitThis summary event means the conditions required to perform a manual transfer to bypass a

Page 6

UPS Alarm and Status Messages95 Liebert® NXL™Max LoadAlarm Ph BThe user adjustable maximum load alarm threshold was exceeded. This is a “notification

Page 7

UPS Alarm and Status MessagesLiebert® NXL™96MMSXferInhibitThis summary event means the conditions required to perform a transfer to bypass are not met

Page 8

UPS Alarm and Status Messages97 Liebert® NXL™OutletOvtempLimitThe difference between the inlet air temperature and the outlet air temperature is too g

Page 9 - SAVE THESE INSTRUCTIONS

UPS Alarm and Status MessagesLiebert® NXL™98RectifierFaultThis summary event indicates a potentially serious condition in the Rectifier circuit. The c

Page 10 - 1.0 INTRODUCTION

UPS Alarm and Status Messages99 Liebert® NXL™RegenTerminatedRegeneration Mode is a service mode that is normally controlled by the service technician.

Page 11 - 1.2 Modes of Operation

UPS Alarm and Status MessagesLiebert® NXL™100SystemCommFailThe control has detected a communication failure of a device on the multi-module communicat

Page 12 - 1.3 Options

UPS Alarm and Status Messages101 Liebert® NXL™System OutputBreaker (UOB)OpenThe system output breaker indicates that it is in the open position.System

Page 13 - 2.0 OPERATION

Introduction3Liebert® NXL™1.2 Modes of Operation1.2.1 Normal ModeOperating in normal mode, the Liebert NXL’s rectifier derives power from a utility AC

Page 14 - Front Doors Removed

UPS Alarm and Status MessagesLiebert® NXL™102NOTES

Page 16

Ensuring The High AvailabilityOf Mission-Critical Data And Applications.Emerson Network Power, a business of Emerson (NYSE:EMR),is the global leader i

Page 17

IntroductionLiebert® NXL™41.3 OptionsA number of options are available from Emerson® for your UPS system. (Some options are not available for all rati

Page 18

Operation5Liebert® NXL™2.0 OPERATIONThe Liebert NXL UPS is equipped with a microprocessor-based display touchscreen designed for convenient and reliab

Page 19

OperationLiebert® NXL™6Figure 3 Main component locations—500kVAU40-5C-2000Rev. 1Option Box(6 Slots)Liebert IntellislotHousingsMain Input CircuitBreake

Page 20

Operation7Liebert® NXL™Figure 4 Main components, 625kVA Liebert NXL, N+1 multi-module unit without static bypassFigure 5 Main components, 625kVA Liebe

Page 21

OperationLiebert® NXL™8Figure 6 Main component locations—750kVA with Static BypassFigure 7 Main component locations—750kVA without Static BypassHMIScr

Page 22 - 2.2 Touchscreen Navigation

Operation9Liebert® NXL™Figure 8 Main components, 1+N multi-module or SMS with static bypass, 1100kVAw UPSFRONT DOORS REMOVEDINPUT CABINET RECTIFIER CA

Page 23 - User Settings

OperationLiebert® NXL™10Figure 9 Main components, 1100kVA UPS N+1 multi-module without static bypassFRONT DOORS REMOVEDMAIN INPUTCIRCUITBREAKER(CB1)OU

Page 24 - Adjustable Setpoints

Operation11 Liebert® NXL™Figure 10 Main Display Screen, typicalFigure 11 Mimic displayBypass Input—Displays the bypass input voltage and the bypass in

Page 25 - 17 Liebert

BATTERY CABINET PRECAUTIONSThe following warning applies to all battery cabinets supplied with UPS systems. Additional warn-ings and cautions applicab

Page 26 - Float Voltage

OperationLiebert® NXL™12Figure 12 Monitor/mimic display example: Normal power flowFigure 13 Monitor/mimic display example: Utility failGreen – NormalO

Page 27 - 2.4 Status Reports Menu

Operation13 Liebert® NXL™Figure 14 Monitor/mimic display example: load on bypass, UPS OnFigure 15 Monitor/mimic display example: load on bypass, UPS m

Page 28 - 2.7 Transfer Menu

OperationLiebert® NXL™142.2 Touchscreen Navigation2.2.1 Main Display ScreenSeveral menu items can be accessed from the main display screen (see Figure

Page 29 - 2.8 Battery Management Menu

Operation15 Liebert® NXL™User SettingsSystem Settings These display settings can be changed from the touchscreen. Press the box to the left of each pa

Page 30

OperationLiebert® NXL™16Adjustable SetpointsThese warning and alarm settings can be changed from the touchscreen. Press the box to the left of each pa

Page 31 - 23 Liebert

Operation17 Liebert® NXL™Battery ManagementThese DC source settings can be changed from the touchscreen. Press the box to the left of each parameter t

Page 32 - 2.12 Reset

OperationLiebert® NXL™18Figure 20 Battery Management ParametersCell Count Adjustment• Cell Count Adjustment— -12 cells to 6 cells (default: 0)Float Vo

Page 33 - 2.14.1 Load on Bypass

Operation19 Liebert® NXL™2.3 Event ManagementThis menu item permits changing how the Liebert NXL handles Alarms, Faults and Status information. Each e

Page 34 - 2.14.2 OK to Transfer

OperationLiebert® NXL™202.5 Startup MenuThis menu is used to start the UPS and individual devices.Manual—This will begin the UPS startup. See 2.15 - M

Page 35 - 2.14.4 Off DC Source

Operation21 Liebert® NXL™2.8 Battery Management MenuThis menu permits configuring DC source settings.Time Remaining Graph—Displays the time remaining

Page 36

iTABLE OF CONTENTSBATTERY CABINET PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2IMPORT

Page 37 - 2.14.7 ECO Mode

OperationLiebert® NXL™22Manual Battery Test—Start/StopManual Battery Equalize—Start/Stop; must be enabled by Emerson Network Power® Liebert® Services

Page 38

Operation23 Liebert® NXL™Figure 26 Battery cycle monitor summary2.9 System View—1+N Systems OnlySystem View will display the status of each of the sys

Page 39 - 31 Liebert

OperationLiebert® NXL™24This button will show the following status of each module in the system:•Comms• Normal—UPS intermodule communication is workin

Page 40 - 2.15.2 Startup—N+1 System

Operation25 Liebert® NXL™2.13 SilenceThis button will silence the audible alarm.2.14 Modes of OperationThis section illustrates the flow of power thro

Page 41 - 2.15.3 Startup—1+N System

OperationLiebert® NXL™262.14.2 OK to TransferThe OK to Transfer status message will be displayed when the bypass line and UPS output power are both av

Page 42

Operation27 Liebert® NXL™2.14.3 Input Power Failure—Load on DC SourceIf the utility AC power source fails or is outside the acceptable range, the DC s

Page 43 - 35 Liebert

OperationLiebert® NXL™282.14.5 Emergency Module Off (Optional)The Emergency Module Off (EMO) mode will transfer the critical load to the bypass line a

Page 44

Operation29 Liebert® NXL™2.14.7 ECO ModeWhen ECO Mode is active, the critical load is supported by the bypass source. The rectifier is On and providin

Page 45 - Retransfer Procedure

OperationLiebert® NXL™302.15.1 Startup—Single Module SystemThis section lists typical step-by-step instructions. The touchscreen will list all steps r

Page 46

Operation31 Liebert® NXL™c. Press OK to continue. This will energize the load on the UPS internal bypass. The message “Close CB1” will appear.d. Close

Page 47 - 39 Liebert

ii2.15 Manual Operations—All Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 292.15.1 Startup—Sin

Page 48

OperationLiebert® NXL™322.15.2 Startup—N+1 SystemThe following instructions will start an individual UPS module. Repeat these steps for all the UPS un

Page 49 - 41 Liebert

Operation33 Liebert® NXL™9. Close all Battery/DC breakers associated with this module. The UPS will stay in this mode until all breakers are closed.Sk

Page 50

OperationLiebert® NXL™34Startup—1+N System with External Maintenance Bypass1. Before applying power to the UPS modules, determine the position of the

Page 51 - 43 Liebert

Operation35 Liebert® NXL™3. If the system has optional Bypass breakers (MBB/MIB), the message “Close MBB” will appear in the multipurpose window.a. Cl

Page 52

OperationLiebert® NXL™36Startup—1+N System Without External Maintenance Bypass1. Before applying power to the UPS modules, determine the position of t

Page 53 - 45 Liebert

Operation37 Liebert® NXL™16. Perform Steps 10 through 14 on the rest of the UPS units in the system ready to be placed on line. This message will appe

Page 54 - UPS System Shutdown

OperationLiebert® NXL™382.15.5 Maintenance Bypass Load Transfers—Single Module SystemFollow these instructions to manually transfer the load between t

Page 55 - 47 Liebert

Operation39 Liebert® NXL™Maintenance Bypass Load Transfers—Single Module System: If Load is on UPS Bypass1. Transfer the UPS system to bypass (see 2.1

Page 56

OperationLiebert® NXL™402.15.6 Load Transfer—N+1 System: Remove UPS from N+1 System (Collective)1. Press the “Transfer” menu button on the touchscreen

Page 57 - 49 Liebert

Operation41 Liebert® NXL™2.15.8 Load Transfer—1+N System: Remove a UPS from System (Collective)1. Under the “Transfer” menu button on the touchscreen,

Page 58 - System Shutdown Procedure

iii3.6 Intelligent Paralleling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 643.6.1

Page 59 - 51 Liebert

OperationLiebert® NXL™422.15.9 Load Transfer—1+N System: Add a UPS to the System (Collective)This section lists typical step-by-step instructions. The

Page 60

Operation43 Liebert® NXL™Figure 42 1+N UPS Transfer to Inverter menu commands

Page 61 - 53 Liebert

OperationLiebert® NXL™442.15.10 Load Transfer—1+N System: Transfer System to Bypass1. Under the “Transfer” menu button on the touchscreen, press the “

Page 62

Operation45 Liebert® NXL™2.15.12 Load Transfer—1+N System: Transfer to Maintenance BypassFollow these instructions to manually transfer the load betwe

Page 63 - 3.0 OPTIONS

OperationLiebert® NXL™462.15.13 Shutdown—Single Module UPS SystemPerform a Module Shutdown to remove power from a UPS module.Read all warnings in 4.0

Page 64 - No Customer Connection

Operation47 Liebert® NXL™2.15.14 Shutdown—N+1 UPS SystemPerform a Module Shutdown Procedure when you want to disconnect power from a UPS module. For S

Page 65 - 123 67894105 111213141516

OperationLiebert® NXL™482.15.15 Shutdown—1+N UPS: UPS ShutdownThis section lists typical step-by-step instructions. The touchscreen will list all step

Page 66

Operation49 Liebert® NXL™Figure 45 1+N UPS shutdown menu commands

Page 67 - 3.4 Digital Load Bus Sync

OperationLiebert® NXL™502.15.17 1+N System ShutdownThis section lists typical step-by-step instructions. The touchscreen will list all steps required

Page 68 - 3.4.5 Master System

Operation51 Liebert® NXL™i. To isolate the system, open all MOB breakers and utility feeds to the bypass and rectifier inputs.Figure 46 1+N System Shu

Page 69 - 3.5 ECO Mode

ivFIGURESFigure 1 Typical single module UPS system one-line diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Figure 2

Page 70 - 3.5.2 Operation

OperationLiebert® NXL™522.16 Automatic OperationsThe Liebert NXL UPS system is designed to function while unattended by an operator. The system contro

Page 71 - 63 Liebert

Operation53 Liebert® NXL™2.16.2 Automatic Transfers to Bypass (Overload Condition)The UPS system will initiate an automatic load transfer to the bypas

Page 72 - 3.6 Intelligent Paralleling

OperationLiebert® NXL™542.16.4 Automatic Retransfers to UPSIn an automatic retransfer, the two circuit breakers (bypass and inverter output) are both

Page 73 - 65 Liebert

Options55 Liebert® NXL™3.0 OPTIONS3.1 Input Contact Isolator BoardThe Input Contact Isolator Board (ICI) provides a Liebert NXL module interface for u

Page 74 - 3.6.6 Module Standby Rotation

OptionsLiebert® NXL™56• Assignment—Custom, Pre-assigned (default: “Input Contact” XY)• Delay, sec—0 to 99.9 (default: 0)• Message—Custom: 0-19 charact

Page 75

Options57 Liebert® NXL™3.2 Programmable Relay BoardThe Programmable Relay Board (PRB) provides a means to trigger an external device when an event occ

Page 76 - 4.0 MAINTENANCE

OptionsLiebert® NXL™583.2.1 Configuring the Programmable Relay Board Settings1. Press Internal Option Settings from the Config menu.2. Press which Pro

Page 77 - 4.2 Liebert Services

Options59 Liebert® NXL™3.3 Remote Alarm Status Panel RASThe Remote Alarm Status Panel (RAS) uses LED status indicators that allow the operator to moni

Page 78 - 4.3 Routine Maintenance

OptionsLiebert® NXL™603.4.2 LBS Configurations• Load Bus Sync – Enable or Disabled (default: Disable)• LBS Master Select - Master or Slave (default: S

Page 79 - 4.4 Battery Maintenance

Options61 Liebert® NXL™3.4.6 Slave SystemAny unit designated as the Slave upon power-up / reset will monitor and lock to the Master LBS Sync Pulse.Whe

Page 80 - Maintenance

vFigure 49 Optional Input Contact Isolator Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56Figur

Page 81

OptionsLiebert® NXL™623.5.2 OperationECO Mode can be started either manually or automatically.Manually—If “Continuos Operation” is enabled under ECO M

Page 82 - 4.7 Corrective Actions

Options63 Liebert® NXL™3.5.3 Bypass Qualification limitsAll of the following conditions must be true to qualify ECO Mode operations based on the bypas

Page 83 - 5.0 SPECIFICATIONS

OptionsLiebert® NXL™643.6 Intelligent ParallelingIntelligent Paralleling is intended to increase system efficiency and reduce operating hours on the m

Page 84 - FCC Class-A Standard

Options65 Liebert® NXL™3.6.2 Intelligent Paralleling Target AreaThe Intelligent Paralleling Target Area is the Number of Redundant Modules that fall b

Page 85 - Software”)

OptionsLiebert® NXL™663.6.6 Module Standby RotationModule Standby Rotation will limit the time a module is in standby operation when the Number of Red

Page 86 - Specifications

Options67 Liebert® NXL™Figure 56 Module standby rotationLoadUPS1 UPS2 UPS3 UPS4 UPS5UPS1 UPS2LoadUPS3 UPS4 UPS5LoadUPS1 UPS2 UPS3 UPS4 UPS5LoadUPS1 UP

Page 87

MaintenanceLiebert® NXL™684.0 MAINTENANCE4.1 Safety PrecautionsObserve the safety precautions in Battery Cabinet Precautions inside the front cover.Ob

Page 88

Maintenance69 Liebert® NXL™4.2 Liebert ServicesStartup, UPS maintenance, DC source maintenance and training programs are available for the Liebert NXL

Page 89

MaintenanceLiebert® NXL™704.3 Routine MaintenanceYou should become thoroughly familiar with the equipment, but at no time should you go beyond the spe

Page 90

Maintenance71 Liebert® NXL™4.3.3 Limited Life ComponentsThe Liebert NXL UPS has a design life well in excess of 10 years. Well-maintained units can co

Page 92

MaintenanceLiebert® NXL™724.4.1 Battery Safety PrecautionsServicing of batteries should be performed or supervised by personnel knowledgeable of batte

Page 93

Maintenance73 Liebert® NXL™Matching Battery Cabinets—OptionalAlthough the individual battery cells are sealed (valve-regulated) and require only minim

Page 94

MaintenanceLiebert® NXL™74Other DC SourcesIf the UPS system uses a DC source other than a factory-supplied Matching Battery Cabinet, perform maintenan

Page 95

Specifications75 Liebert® NXL™5.0 SPECIFICATIONS5.1 DC Sources5.1.1 Battery OperationThe separate battery manufacturer’s manual, available on the manu

Page 96

SpecificationsLiebert® NXL™76Table 9 Electrical specificationsInput ParametersInput Voltage to Rectifier, VAC,3-phase, 3-wire480V/575V/600VInput Volta

Page 97

Specifications77 Liebert® NXL™Disclosures with Regard to Embedded Software Licensed from Nokia, Inc., (“Sublicensed Software”)1. Limits on Use, Distri

Page 98

SpecificationsLiebert® NXL™78

Page 99

UPS Alarm and Status Messages79 Liebert® NXL™APPENDIX A-UPS ALARM AND STATUS MESSAGESTable 10 shows alarm and status messages as they appear in the Li

Page 100

UPS Alarm and Status MessagesLiebert® NXL™80Batt DischargingThe UPS is on Battery.The most common reason for going to battery is a loss of Rectifier i

Page 101

UPS Alarm and Status Messages81 Liebert® NXL™Batt Ovtemp LimitOne or more of the Battery Temperature Sensors is reporting a temperature above the limi

Page 102

Important Safety Instructions1Liebert® NXL™IMPORTANT SAFETY INSTRUCTIONSSAVE THESE INSTRUCTIONSThis manual contains important instructions that should

Page 103

UPS Alarm and Status MessagesLiebert® NXL™82Batt Temp ImbalanceWith more than one Battery Temperature Sensor installed, the controls are detecting too

Page 104

UPS Alarm and Status Messages83 Liebert® NXL™BPSS Start InhibitWhen starting the module BPSS's in a 1+N system without a MBB, there are not enoug

Page 105

UPS Alarm and Status MessagesLiebert® NXL™84BypOverloadPh CThe critical load is greater than 110% while the UPS is on bypass. The controls may shut th

Page 106

UPS Alarm and Status Messages85 Liebert® NXL™DC LinkGnd Fault-The negative DC Bus has a ground fault.The UPS controls monitor the DC Bus negative half

Page 107

UPS Alarm and Status MessagesLiebert® NXL™86EMOShutdownAn Emergency Module Off (EMO) command has been detected.The EMO signal means the front panel EM

Page 108

UPS Alarm and Status Messages87 Liebert® NXL™ExcessAutoRexfersThe UPS has tried to reconnect the inverter to the critical bus too many times. For a si

Page 109

UPS Alarm and Status MessagesLiebert® NXL™88InletOvtempThe air flowing into the UPS is too warm.This alarm is self-clearing. When the condition is no

Page 110 - UPS Alarm and Status Messages

UPS Alarm and Status Messages89 Liebert® NXL™InputCurrentLimitAn active Input Current Limit alarm means the detected input current (RMS) exceeds the l

Page 111

UPS Alarm and Status MessagesLiebert® NXL™90Inv OverloadPh BAn overload condition is active on B phase.B phase load condition exceeds 105%.A countdown

Page 112 - SL-25425_REV9_08-13

UPS Alarm and Status Messages91 Liebert® NXL™LBS Active - MasterThis UPS system has been enabled as the functional Master Load Bus Synchronization (LB