Wiring and Connections - Main Board
Liebert
®
Universal Monitor
20
4.0 WIRING AND CONNECTIONS - MAIN BOARD
4.1 Wiring Specifications
Input and output connections to the Liebert Universal Monitor may be made in any order—it is not
necessary, for example, to make all input connections before making any output connections. Use
copper conductors only for all wiring.
!
CAUTION
Switch OFF electric power to the Liebert Universal Monitor before installing any wiring to
the unit or changing input or output connections. The Power On/Off switch is in the top left
corner of the unit, just below the battery pack.
Table 7 Wiring specifications - main board
Connection Supported Wire Type Maximum Wire Length Rating
Digital
Input
18-22 AWG Stranded & Unshielded
18 AWG* (recommended)
Non Plenum - Belden 9740
Plenum - Belden 89740
750 ft. (225m)
Dry Contact
(24VDC,
10 mA)
Digital
Output
18-22 AWG Stranded & Unshielded
18 AWG* (recommended)
Non Plenum - Belden 9740
Plenum - Belden 89740
18 AWG*
(recommended)
20 AWG 22 AWG
24VAC@3A
@3A 50 ft. (15m)
@2A 100 ft. (30m)
@1A 200 ft. (60m)
@3A 40 ft. (12m)
@2A 60 ft. (18m)
@1A 100 ft. (30m)
@3A 25 ft. (7m)
@2A 35 ft. (10m)
@1A 75 ft. (23m)
Analog Input
2-Wire
Transducer
18-22 AWG Stranded & Unshielded
18 AWG* (recommended)
Non Plenum - Belden 9740
Plenum - Belden 89740
750 ft. (225m)
4-20 mA Signal
Input Selectable
Power Source
(12/24VDC)
Analog Input
4-Wire
Transducer
18-22 AWG Stranded & Unshielded
18 AWG* (recommended)
Non Plenum - Belden 8489
Plenum - Belden 88489
750 ft. (225m)
4-20 mA Signal
Input Selectable
Power Source
(12/24VDC)
Common
Alarm
Output
18-22 AWG Stranded & Unshielded
18 AWG* (recommended)
Non Plenum - Belden 9740
Plenum - Belden 89740
18 AWG*
(recommended)
20 AWG 22 AWG
24VAC
@3A
@3A 50 ft. (15m)
@2A 100 ft. (30m)
@1A 200 ft. (60m)
@3A 40 ft. (12m)
@2A 60 ft. (18m)
@1A 100 ft. (30m)
@3A 25 ft. (7m)
@2A 35 ft. (10m)
@1A 75 ft. (23m)
Communication
RS232
Null Modem Cable 50 ft. (15m) N/A
Communication
EIA422
Liebert
SiteScan
®
18-22 AWG Stranded & Shielded
22 AWG* (recommended)
Non Plenum - Belden 9461
Plenum - Belden 88761
1000 ft. (300m) N/A
Communication
EIA485
18-22 AWG Stranded & Shielded
22 AWG* (recommended)
Non Plenum - Belden 9461
Plenum - Belden 88761
3000 ft. (900m) N/A
Phone/Modem
Line
4 Wire (Pins 3 & 4)
RJ11 Connector
N/A N/A
24VAC Power
Connection
(TB7)
18-22 AWG Stranded & Shielded
18 AWG* (recommended)
Non Plenum - Belden 8770
Plenum - Belden 88770
150 ft. (45m)
24VAC
@1.3A
Power Connections (Transformer Module)
115VAC
14 AWG Stranded & Unshielded
Non Plenum - Belden 5101UE
150 ft. (45m)
115VAC
@4A
230VAC
14 AWG Stranded & Unshielded
Non Plenum - Belden 5101UE
150 ft. (45m)
230VAC
@0.5A