Installing a Liebert iCOM Unit-to-Unit Network
87 Liebert
®
iCOM
®
for Liebert DSE
Wall-Mount Large Display
Only large displays can be used for remotely monitoring and controlling cooling units connected on
the same network. Each wall-mount large display requires 120VAC or 230VAC input power;
Emerson
®
provides an AC adapter wall plug. A straight-through Ethernet cable must be connected
between the network switch and the P64 port on the back of the display. This will enable control and
monitoring capabilities to any cooling unit connected to the network.
Figure 61 Wiring a large display for U2U network operation
Crossover
Coupler
(if provided)
Ethernet Cable
Liebert iCOM
I/O Board
Straight-Through
Ethernet Cables
(If coupler is not provided, connect
one end plug to P64 of large graphics
display and the other end to the
Liebert iCOM I/O board)
CAN
Cable
See Note 4
Optional Large
Graphics Display
(Rear View)
To / From Other
Networked Units
U2U Networking Switch
(Field-Supplied)
Not
Used
Customer Connection Point
(if provided)
P64A Connection
(if provided)
Near I/O Board