Emerson Liebert ICOM-DO User Manual Page 125

  • Download
  • Add to my manuals
  • Print
  • Page
    / 172
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 124
Service Menu Parameters
117 Liebert
®
iCOM
®
for Liebert DSE
S199 - Operation @ Sensor Failure—This parameter determines what action to take if the static
pressure sensor fails (non-teamwork). There are two options to use when handling a static pressure
sensor failure, they are SP OFF = static pressure control Off, where the control will use S146 to
control the fan when the sensor is lost or Freeze Speed = keep the fanspeed unchanged based on the
last reading to iCOM. Things that need to override fanspeed such as freeze protection can still change
the fanspeed.
S19A SP Upper Range—The control calculates the Upper Range by using S191 “SP Setpoint” and
S192 “SP Deadband,” the results on lines show both values, in WC and Pa.
S19B SP Lower Range—The control calculates the Lower Range by using S191 “SP Setpoint” and
S192 “SP Deadband,” the results on lines show both values, in WC and Pa.
Service—Unit Diary Menu Screens (Large Display Only)
Unit Diary—Shows all entered program changes and maintenance performed on the unit. The Unit
Diary serves as a note pad, where information can be added through the Liebert iCOM Service Tool.
8.2 Service—Standby Settings / Lead Lag Menu Screen
Standby Settings / Lead Lag allows the user program lead-lag setup when units are connected in a
Liebert iCOM U2U network.
Figure 91 Standby settings / lead-lag screen
S502 Number of Standby Units—Selects the number of units that will be in Standby mode. When
a unit is in standby mode, the fan will be Off and no cooling will be provided.
S503 Rotation Frequency—Controls when a rotation will occur between the standby units and the
operating units within a network.
S504 Rotate at—Sets the hour and minute of the rotation.
S505 Rotate by—Determines the number of positions to rotate by. Example: If there are six units in
a unit-to-unit network and units 1, 3 and 5 are in standby and this parameter is set to “1,” then at the
next rotation units 2, 4 and 6 will be placed in standby and units 1, 3 and 5 will become operational.
S506 Stdby Fan Timer at Reheat/Hum—Sets the time that the fan will operate after a unit enters
standby or sleep if the reheat or humidifier was operating when commanded to turn Off. Default is 30
minutes; range is 3 to 360 minutes.
S507 Perform one Rotation—Setting this parameter to YES will perform one rotation without
waiting on the rotation timer to expire.
Page view 124
1 2 ... 120 121 122 123 124 125 126 127 128 129 130 ... 171 172

Comments to this Manuals

No comments