Emerson Liebert ICOM-DO User Manual Page 157

  • Download
  • Add to my manuals
  • Print
  • Page
    / 172
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 156
Service Menu Parameters
149 Liebert
®
iCOM
®
for Liebert DSE
8.9 Service-System/Network Setup Menu Screens
System Network Setup allows setting up a unit-to-unit (U2U) network for multiple cooling units
controlled by Liebert iCOM.
Figure 134 System/network setup screen—System, page 1 of 2 (large display only)
S802 Number of Connected Units—Reflects the number of units connected that to the Liebert
iCOM large display. If multiple units are connected in a unit-to-unit network, then the number will be
greater than one.
S803 Teamwork Mode—Selects which teamwork mode to use within a selected group. Teamwork
modes are described in 4.0 - Teamwork.
S804 Teamwork is based on—Choices are Average or Maximum
Average: The temperature/humidity is controlled to an average reading of the controlling
sensors.
Maximum: The temperature/humidity is controlled to the highest controlling sensor reading.
S805 Qty Units Included in Average—Defines the number of units to include in the average
calculation. If the Qty setting is higher than the number of units, use all teamworked units in the
group for the calculation. Available only if Teamwork Mode Based On is set to Average.
S808 Lock for Upgrade—Used to save and update files for Liebert iCOM service tool updates.
Service tool updates are performed by specially trained and certified HVAC technicians.
S809 Configuration Safe—Saves or loads configuration settings for the display that have been
modified from the defaults to an internal file that can be downloaded / uploaded using the Liebert
iCOM Service Tool. Selecting “Save” will write the settings to the internal storage file and selecting
“Load” will write the settings from the internal storage file to the application software. The internal
file is updated every 12 hours automatically.
S810 Network Safe—Saves or loads network settings for the display that have been modified from
the defaults to an internal file that can be downloaded/uploaded using the Liebert iCOM Service Tool.
Selecting “Save” will write the settings to the internal storage file. Selecting “Load” will write the
settings from the internal storage file to the application software.
S811 SW Version—Contains the application software version loaded onto the Liebert iCOM display.
Page view 156
1 2 ... 152 153 154 155 156 157 158 159 160 161 162 ... 171 172

Comments to this Manuals

No comments