Service Menu Parameters
127 Liebert
®
iCOM
®
for Liebert DSE
Figure 103 Diagnostics/service mode screen, page 3 of 8
S324 Electric Heat 1 (or HG/HW)—Activates Stage 1 of the unit’s reheat system.
S325 Electric Heat 2 (or HG/HW)—Activates Stage 2 of the unit’s reheat system.
S326 Electric Heat 3 (or HG/HW)—Activates Stage 3 of the unit’s reheat system.
S327 SCR Heat—Specifies the pulse width the heating system should run at on units using silicon
controlled rectifier type reheat.
S328 Dehumidification Output—(Read Only) On/Off status of dehumidification.
S329 Humidifier Fill—Activates the humidifier water source solenoid valve, which fills the
humidifier pan or canister with water.
S330 Humidifier—Activates the humidifier system in its entirety.
S331 Humidifier Drain (Liebert HPM
only)—Activates the humidifier drain solenoid, allowing
water to drain from the canister if the unit is equipped with an optional the steam generating
humidifier.
S332 Humidifier Current (Liebert HPM
only)—Shows the amount of AC amperes the humidifier
is consuming if the unit is equipped with an optional steam generating humidifier.
S333 Q15 Output State—Indicates the status of Q15 output.