Operation
39 Liebert
®
iCOM
®
for Liebert DSE
Tandem Digital Scroll Operation for Dehumidification
When tandem digital scroll compressors are present, the activation and deactivation of
dehumidification will be handled just as it would for conventional compressor operation. The rules
described in this section apply only when dehumidification is active. Further, the activation or
deactivation of compressors for certain alarm conditions, or Suction Pressure Management, take
precedence over the rules described in the ensuing subsections.
The Digital Scroll Ramping % for dehumidification will be overridden by the activation of the
following routines
Suction Pressure Management (“Freeze Protection”)
Winter Start (S403 Low Pressure Alarm Delay)
Capacity Reduction for High Pressure
Tandem Temporary Digital Loading
Dehum low limit threshold
When the system goes into dehumidification mode, the sequencing of the compressors and the Digital
Scroll ramp selections become fixed, as does the lead-lag order of the tandem banks. This sequence is:
Comp 1A
Comp 2A
Comp 2B
Comp 1B
The compressor activation / deactivation points may be adjusted, but they cannot be adjusted so that
the compressor sequence is changed; C2B’s settings cannot be adjusted so that it will turn On before
C1B during dehumidification. The only time sequencing will be adjusted is when compressor alarms
are present during dehumidification. Please consult the corresponding sections below for details on
this mode of operation.
The compressor settings for dehumidification will be visible in the “Tandem Digital Dehum” menu,
which is accessible from the Advanced – Expert Settings menu.
Because of the specialized nature of Tandem Digital Scroll Dehumidification, the setting on line A2
(“Dehumidification with Comp”) will have no effect for dehumidification with Tandem Digital Scroll
Compressors.
Dehumidification Control Details for Return (Normal) Dehum
The Liebert DSE is designed for sensible cooling, so the number of compressors available for
dehumidification are limited by the cooling load.
Dehumidification Entry Criteria
When the call for dehumidification goes above the “RET Dehum: CFD% to start Dehum” parameter
on line A558, the initiation of dehumidification and the compressors it will activate is based on
whether dehumidification was last made inactive by Low Limit 2 (line S133).