ControlWave Micro Instruction Manual (CI-ControlWave Micro)
3-4 I/O Modules Revised Jun-2013
Use AWG 14 or smaller wire (consult with the field device
manufacturer for recommendations) for remote terminations. Leave
some slack and plan for wire routing, identification, and maintenance.
Route the cables running between the I/O module and the DIN-rail
mounted terminal blocks out through the bottom of the I/O module
assembly via the bezel assembly.
Figure 3-2. Module Wiring: Remote Termination
3.2.3 Shielding and Grounding
Use twisted-pair, shielded and insulated cable for I/O signal wiring to
minimize signal errors caused by electromagnetic interference (EMI),
radio frequency interference (RFI), and transients.
When using shielded
cable, ground all shields at only one point in the appropriate system.
This prevents circulating ground current loops that can cause signal
errors.