Service Menu Parameters
Liebert
®
iCOM
®
182
Example:
X = Auxiliary Weighting in TW AVG
T0= The temperature reported by the master
n= number of units in the group
T1 through Tn = the wired sensors connected to each unit in the U2U group. The temperature
reported by each unit is based on the Individual Remote Sensor Mode and Unit Remote Sensor
Mode/AVG incl.
The aggregate average value will be:
(X/100)(Actual Auxiliary Air Temperature) + [(100-X)/100/(n+1)](T0 + T1 + … Tn)
SB21 Auxiliary Use in TW Max—Determines how the Raw Auxiliary Air Temperature is used in
teamwork. This menu item has three possible values:
Exclude (default)—the Actual Auxiliary Air Temperature value will not be included in the
maximum calculation.
Include— the Actual Auxiliary Air Temperature value will be included with values from the
master and all other units in the teamwork group in order to calculate the maximum value.
Only—the Actual Auxiliary Air Temperature maximum value will be the AAT value, i.e. values
from the master and all other units in the teamwork group will be ignored.
The parameter will be hidden unless Teamwork is based on is set to Maximum.
SB22 AAT Fallback Timer—Serves as a fail-safe mode if the wireless proxy fails to communicate
with the Liebert iCOM. The user-adjustable timer begins when communication is lost. Once it reaches
zero, the control will revert to wired sensor control. The default setting is 60 seconds with an
adjustable range of 0-999 seconds.
8.14 Service-Expansion Device Setup Menu Screens
The Expansion Device Setup menu is used to set up auxiliary modbus devices, such as power meters.
This menu is not used for establishing communication with the BMS.
Figure 175 Expansion device, page 1 of 3
SC03 Modbus Baud Rate / Parity—Configures the baud rate and the parity for communication
with connected devices. The baud rate may be set to 1200, 2400, 4800, 9600 or 19200. The parity may
be None, Even or Odd.
SC04 Modbus Mode / Requested State—The left hand parameter configures the Modbus Mode.
The right hand parameter is a user-adjustable value to enable or disable communication. The mode
may be ASCII or RTU.
SC05 Actual Modbus State—Read-only value displays the device connection state.