Service Menu Parameters
Liebert
®
iCOM
®
160
Figure 153 Sensor calibration/setup screen, page 5 of 12
Each unit can be equipped with a total of 20 rack sensor readings or ten 2T temperature sensor
modules. These menus permit temperature sensor calibration by entering a negative or positive
offset.
The calibrated reading is displayed in the far right column. If a value does not appear in the far right
column, then the sensor is either not set up correctly or is not connected.
Figure 154 Sensor calibration/setup screen, page 6 of 12
S657 DP Transducer is Connected to—Sets the analog input that will be used for the differential
pressure transducer. This parameter is selectable from None, Ana In 1, Ana In 2, Ana In 3 and
Ana In 4. The factory default is none.
S658 DP Transducer is Setup in—Sets the unit of measure that will be used for the differential
pressure transducer. This parameter is selectable in inWC or PA. The factory default is PA.
S659 DP Transducer Low—Sets the unit of measure that will be used for the low differential
pressure transducer. This parameter is selectable from 0-9.999 inWC. The factory default is 0.000
inWC.
S660 DP Transducer High—Sets the unit of measure that will be used for the high differential
pressure transducer. This parameter is selectable from 0-9.999 inWC. The factory default is 2.005
inWC.