Operation
29 Liebert
®
iCOM
®
3.2.4 Fluid Temperature Monitoring
Two supply and two return chilled water temperature sensors may be added per unit for local and
remote monitoring of water temperature differential temperature. Temperature is monitored with 2T
sensors (two sensors on dual circuit units).
The first step in setting up the additional supply sensors is to program the DIP switches using
Table 5 below. The DIP switches may be access by removing the rear housing or through the precut
hole in the housing. See Figure 69 for additional information.
Figure 24 DIP switches in 2T sensors
After setting the DIP switches, see 4.3.3 - Terminate the Final Sensor on the CANbus Link to
complete the sensor installation.
Once the sensors have been connected, go to Service Menus> Sensor Calibration/Setup (Figure 149).
Locate the line that reads Chilled Water Sensor Type. Change the right hand parameter to 2T or Dual
2T. Verify the fluid inlet and outlet temperature readings with a field-supplied temperature sensor.
Compare the values measured with the meter and calibrate the temperatures as needed. Use the CW
Temp Sensor C1 / C2 Placement feature to swap the inlet and outlet temperatures shown in the
Liebert iCOM if the sensor probes are reading backward when measured with a field-supplied meter.
(Supply in the Liebert iCOM represents the actual return or vise versa).
3.2.5 Fluid Flow Monitoring
Fluid flow meters are available for monitoring fluid flow in
gallons per minute or liters per minute. When the flow meter is
coupled with fluid temperature sensors, Liebert iCOM will
calculate real time cooling capacity in kW or kBTU/Hr. Unit flow
rate and capacity may be hidden or shown from the unit view and
monitored through the Liebert IntelliSlot Unity Card. Contact
your local Emerson representative to obtain a flow meter.
3.3 Temperature Control
The temperature control parameters are in Service > Setpoints. The Temperature Setpoint parameter
is in both the User Menu and Service Menu under Setpoints.
The Liebert iCOM has two temperature control types:
Proportional
•PI
Intelligent (chilled water models only)
Each control type affects the timing and intensity of the cooling/heating operations. The Control Type
parameter is in Service>Setpoints.
Table 5 DIP switches in 2T sensors
CANbus
Node ID
DIP switch Position
12345678
Fluid Circuit 1 30 Off On On On On Off Off Off
Fluid Circuit 2 31 On On On On On Off Off Off
Circuit 1 and 2 fluid sensors are dual purpose CANbus ID’s in software. These sensors also may be used for supply temperature
monitoring of the conditioned space. Before considering installing fluid sensors, verify that the 2T supply sensors are not being
used. See the Service Menus, Sensor calibration, page 11 of 12 for more information. Adding duplicate sensors will result in
sensor communication loss.
Switch Up = ON
Switch Down = OFF