Operation
41 Liebert
®
iCOM
®
3.5 Liebert Air Economizer
Operation
Liebert cooling units control the Liebert Air Economizer with the analog outputs of the Liebert iCOM
control. The Liebert iCOM can be used with a Liebert Air Economizer or with a air economizer
supplied by others if equipped with 0-10VDC or 2-10VDC dampers. The Liebert iCOM is capable of
driving two independent damper motors or can be set up through the software to output a single
signal where the dampers are inversely driven.
The primary cooling unit responds to sensors that monitor the temperature and humidity of the
outdoor air, return air and supply air. If outdoor conditions are within the tolerances set, the primary
cooling unit opens the Liebert Air Economizer’s dampers varying amounts to use outdoor air for
cooling. When outdoor conditions are too warm or humid for cooling, the primary cooling unit closes
the Liebert Air Economizer’s dampers, taking it out of the cooling process. Humidification and
dehumidification are disabled when the Liebert Air Economizer is operating.
NOTICE
Risk of high or low humidity. Can cause environmental conditions that are outside equipment
requirements.
While the Liebert Air Economizer is operating, the primary cooling unit’s humidification and
dehumidification are inhibited. If humidity level is important to operational requirements, it
must be controlled by other methods during operation of the Liebert Air Economizer. While
the primary cooling unit is cooling without the Liebert Air Economizer, the primary cooling
unit will control humidity levels according to its setpoints.
NOTICE
Risk of freezing temperatures. Can cause equipment and property damage.
Low outdoor temperatures can produce freezing conditions that adversely affect cooling
systems employing water, particularly when the water is not moving through the pipes. When
cooling system water is not moving, frozen waterlines, burst coils and water damage are
possible. The outside damper must be set so that it is fully closed when freezing temperatures
are possible and the cooling system is not operating (see 3.5.3 - Disable the Liebert Air
Economizer). This can be achieved by either connecting a freeze stat that interrupts the
economizer signal or by wiring a freeze stat directly into the Liebert iCOM’s customer input.
The risk of freezing is increased unless the proper amount of glycol is added to the chilled
water unit loops.
NOTICE
Risk of infiltration of odors, smoke and particulates from outside air. Can cause
environmental conditions that are outside equipment requirements.
The Liebert Air Economizer does not remove odors, smoke, gases or particulates from the
outside air used for cooling. These must be controlled by other methods.
When the Liebert Air Economizer is being used for cooling, both the outside air damper and the room
return air damper are active in an opposing relationship. The cooling requirement and temperature of
the outdoor air will determine the position of the outside air damper. It will range from fully closed to
fully open. As the outside air damper moves toward fully open, the return air damper will close to a
minimum of 15%. The 15% minimum is to make sure that air remains circulating near the return air
sensor. If the return air sensor is moved to another position where there is constant circulation of air
in both outdoor and indoor modes, then the minimum 15% indoor damper position can be removed.
NOTICE
Risk of improper operation. Can cause degraded cooling and ventilation operation because of
improper building air pressure.
The incoming air from the outside damper requires expelling an equal volume of air through a
field-provided powered relief air vent. The volume that must be expelled will vary from 0 to
80% of the total airflow for all Liebert Air Economizer
units. The powered relief system
should be sized for 80% of the total airflow for all Liebert Air Economizer units in the
conditioned space and to maintain minimal building air pressure.