User Menu Parameters
Liebert
®
iCOM
®
120
Configuring Low Noise Operation
First, determine the days and time of day low noise is required. This will be set U806 through U808
respectively. Second, determine the maximum fan speed setting during low noise operation.
In this example, the user does not want fan speed to exceed 35% max speed from 10 pm to 8 am
weekdays.
1. Set U805 Mon-Fri columns to yes.
2. Set U806 interval time from 22:00 to 8:00
3. U807 = 0% / 100%
4. U818 = 35% (Max fan speed low noise)
5. U819 = 100% (Max fan speed during normal operation)
The settings above result in a 35% maximum speed when the timer is active (i.e., at night) and will
operate the fan between 0 and 100% maximum speed of when the timer is inactive (normal operation,
during daytime).
7.9 User-Expansion View Menu Screens
The Expansion View menu applies to Liebert Thermal management units with Modbus Power Meter.
This menu allows the user to see the connection status, voltage, operating current and power for up to
six devices per unit.
Figure 104 Expansion Device View, page 1
Device Name
Device
Connection
State
Phase
Current
Total Power Used in
kWh by All
Connected Devices
Total Watts
Measured by All
Connected Devices
Voltage L1-N, L2-N
and L3-N
Power Consumed
in kWh
Total Watts
Voltage L1-L2, L2-L3
and L3-L1
Incoming Voltage
Type
Page view 129
1 2 ... 125 126 127 128 129 130 131 132 133 134 135 ... 195 196

Comments to this Manuals

No comments