Emerson Liebert iCOM User Manual Page 57

  • Download
  • Add to my manuals
  • Print
  • Page
    / 196
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 56
Operation
47 Liebert
®
iCOM
®
Outdoor Sensor Sharing
When multiple cooling units with Liebert iCOM and Liebert Air Economizer are networked, the
control can be set up to share the outside air sensors of all the units connected in the U2U group.
Outdoor air sensor sharing is enabled on SA16. When set to Shared, all the outdoor temperature and
humidity readings are averaged among all connected units. The average calculation is used to
determine air economizer eligibility on lines SA04 through SA06.
Upon startup after a loss of power to the Liebert iCOM control board, the main fan will operate at
100% for 5 minutes. After the fan has run at 100% for 5 minutes, the standard fan control will be able
to modulate the fan. For other control modes, refer to Variable Speed Fans—EC or Variable
Frequency Drives on page 20.
3.5.3 Disable the Liebert Air Economizer
The Liebert Air Economizer can be disabled using a hard-wired deactivation switch, through the
iCOM display, or through a remote monitoring system using a Liebert IntelliSlot
®
card.
A field-installed and wired normally closed deactivation switch may be connected to Terminals 24 and
51 in place of the factory-supplied jumper. Removing a factory-installed jumper will deactivate the
unit’s air economizer function (see Figure 41) and produces an FC Lockout warning. A normally open
deactivation switch may also be used. Line S227 of the Service Menu > Set Alarms must be changed
from Opened to Closed.
The Liebert Air Economizer may be disabled by changing SA02 Enable Economizer to No.
The Liebert Air Economizer may be disabled through a remote monitoring system by writing a
disable command to data label Air Economizer Control. When disabled, SA02 status will read No. The
building management system may override SA04 through SA07 by writing an enable command.
When the enable command is written, SA02 will read Remote. Refer to the Liebert IntelliSlot
®
Modbus 485, Modbus IP and BACnet IP Reference Guide, SL-28170, for additional information. The
manual is available at the Liebert Web site: www.liebert.com
Deactivating the Liebert Air Economizer will transfer all cooling to the secondary source.
Air Economizer Remote Status Indication
The K11 relay can be activated when the Liebert iCOM determines that the conditions are acceptable
for the Liebert Air Economizer
to operate. This relay will remain active during a BMS remote
deactivation of the Liebert Air Economizer.
Figure 41 Deactivation switch
NOTE
Lines S137 through S141 are not applicable to the Liebert Air Economizer.
24 51
Liebert Air Economizer
Deactivation Switch
Terminals 24 and 51
Factory-Installed Jumper
Customer must remove jumper
and connect normally closed
contact to Terminals 24 and 51.
Open the contact to deactivate
the Liebert Air Economizer
functionality.
Main unit will continue to run without
the Liebert Air Economizer feature.
DPN001449
Pg. 6, Rev. 2
Page view 56
1 2 ... 52 53 54 55 56 57 58 59 60 61 62 ... 195 196

Comments to this Manuals

No comments