34 Chapter 4 Operator Control And Display Panel
Liebert APM Modular UPS User & Installation Manual
Alarm Explanation
Alarm silence SILENCE ON/OFF key pressed
Turn on fail
Inverters failed to turn on when the INVERTER ON key was pressed. This may be the result of an
invalid operation (maintenance bypass on) or DC bus or rectifiers not ready
Alarm reset FAULT CLEAR or SILENCE ON/OFF key pressed
Bypass mode The UPS is in bypass mode
Normal mode The UPS is in normal mode
Battery mode The UPS is in battery mode
Check UPS output UPS shutdown with no output power
Generator connected Generated connection signal is received
BCB open BCB status (open)
BCB closed BCB status (closed)
Battery float charging Battery status (float charge mode)
Battery boost charging Battery status (boost charge mode)
Battery discharging Battery status (discharge mode)
Battery period testing The battery is under automatic periodic battery maintenance test (20% capacity discharge)
Batt. capacity testing The user initiated a battery capacity test (100% capacity discharge)
Batt. maint. testing The user initiated a maintenance test (20% capacity discharge)
UPS system testing The user initiated a UPS self-test
Inverter in setting Inverters starting up and synchronising
Rectifier in setting Rectifiers starting up and synchronising
MBP-T cabinet Fans Fault Maintenance bypass cabinet fan fault
Ext Input TX Overtemp External input isolation transformer overtemperature
Ext Output TX Overtemp External output isolation transformer overtemperature
Battery Room Alarm Environment in battery room needs attention
Battery reverse Connect the battery again and check the battery cable connection
No battery Check the battery and the battery cable connection
Auto start After the UPS shut down at EOD, the inverters automatically start upon mains restoration
REC FLASH UPDATE Rectifier software is being updated
INV FLASH UPDATE Inverter software is being updated
MONITOR FLASH UPDATE Monitor software is being updated
Input contactor fault Input contactor fault
Contactor P.S. 1 fault Contactor power supply board 1 fault
Contactor P.S. 2 fault Contactor power supply board 2 fault
DSP firmware error The inverter software does not match the rectifier firmware
SPM Board Not Ready
The acquisition board is not properly connected. Seek technical assistance from the local
customer service center of Emerson
SPM CRC Check Error
Data check error of acquisition arithmetic module. Seek technical assistance from the local
customer service center of Emerson
SPM Branch Curr Over LL
Load too large, exceeding route current low threshold (set by commissioning engineer, 60% of
rated route current by default)
SPM Branch Curr Over HL
Load too large, exceeding route current high threshold (set by commissioning engineer, 80% of
rated route current by default)
SPM Branch Over Current
Load too large, exceeding route overcurrent point (set by commissioning engineer, 105% of rated
route current by default)
SPM Branch 1 Inrush OC
Load too large, exceeding route impact overcurrent point (set by commissioning engineer, 130%
of rated route current by default)
SPM Branch Breaker Fail
Output distribution switch open. Check whether it was caused by human intervention or fault.
Check the load if was caused by fault
SPM Internal Comm Failure Power interruption between bypass module and SPM monitoring module
SPM Maitainance Bypass
Breaker Close
The maintenance bypass switch of the UPS is closed
SPM Output Breaker Open The output switch of the UPS is open
Note: If the alarms are caused by the values set by the Emerson-authorized commissioning engineer using the configuration
software, and the user need to change the setting values, please contact the local customer service center of Emerson