Chapter 5 Service
This chapter introduces the UPS service, including the service procedures of the power module, bypass module and
output distribution module, and the replacement of air filter.
5.1 Replacement Procedures Of Power Module, Bypass Module And Output
Distribution Module
5.1.1 Notes
1. Only the customer service engineers shall service the power modules, bypass module and output distribution
modules.
2. Remove the power modules, bypass module and output distribution modules from top to bottom, so as to prevent
cabinet toppling due to high centre of gravity .
3. To ensure safety, before servicing the power modules and bypass module, be sure to use a multimeter to verify
that the DC bus capacitor voltage is lower than 60Vdc, and that the voltages between the earth and the components
you are going to work on are under dangerous voltage values, that is, lower than 60Vdc or 42.4Vac peak value.
4. The static bypass module is not hot pluggable. It should be replaced only when the UPS is in maintenance bypass
mode or completely powered off.
5. The power modules and bypass module should be serviced five minutes, and installed in the cabinet again 10
minutes, after they are removed.
5.1.2 Power Module Replacement Procedures
Provided that the UPS is in normal mode, and that the bypass is normal:
1. Press and hold the INVERTER OFF key on the operator control and display panel for two seconds to manually turn
off the inverters, and the UPS transfers to bypass mode.
2. Place the ready switch on the front panel of the power module to the up position (i.e., in unready state).
3. Two minutes later, remove the fixing screws on both sides of the front panel of the module, and pull the module out
of the cabinet.
Note: The module will be blocked by a spring piece at the left side of the module when the module is pulled out of the
cabinet halfway. At this point, you must press the spring piece before you continue to pull the module out.
4. After servicing the module, confirm that the DIP switch of the module is set correctly, and that the ready switch is in
unready state.
5. Push the module (at least 10s after another) into the cabinet, and tighten the screws on both sides.
6. Wait for two seconds, place the ready switch of the module to the down position, and the module is ready. Then the
module will be added into the system automatically and begin to work.
5.1.3 Power Module Service Procedures
Provided that the UPS is in normal mode, and that the bypass is normal:
1. Press and hold the INVERTER OFF key on the operator control and display panel for two seconds to manually turn
off the inverters, and the UPS transfers to bypass mode.
2. Close the maintenance bypass, and the UPS transfers to maintenance bypass mode.
3. Open the UPS output switch and input switch.
4. Press the EPO switch, and open the battery circuit breaker (BCB).
5. Remove the fixing screws on both sides of the front panel of the bypass module, and pull the module out of the
cabinet.