8 Chapter 1 Installation
Liebert APM Modular UPS User & Installation Manual
at the rear of the UPS cabinet. Tighten the output neutral bar connections to 5Nm (M6 bolt). Ensure correct
phase rotation.
z
In case output distribution modules are not installed, please connect the output cables between the output
terminals in the front of the UPS cabinet and the loads, and connect the output earth cable to the output earth
terminal at the rear of the UPS cabinet.
Warning
If the load equipment will not be ready to accept power on the arrival of the commissioning engineer, ensure that the system
output cables are safely isolated at their ends.
7. Replace the protective cover.
1.6.4 Optional Matching Battery Cabinet
The matching battery cabinet structure is shown below.
Figure 1-4 Battery Cabinet Outline Drawing