22 Chapter 3 Operating Procedures
Liebert APM Modular UPS User & Installation Manual
Battery start button
Figure 3-2 Location of battery start button
3.3 Procedures Of Transfer Between Operation Modes
3.3.1 Transfer From Normal Mode To Battery Mode
Open the input switch to cut off the mains input, and the UPS enters battery mode. To return to normal mode, wait a
few seconds and close the input switch to connect the mains power to the UPS. The rectifiers will restart
automatically after 10 seconds and resume feeding power to the inverters.
3.3.2 Transfer From Normal Mode To Bypass Mode
Press and hold the INVERTER OFF key for two seconds to transfer the UPS to bypass mode.
Note
In bypass mode, the load is being powered by the mains input and is not receiving conditioned power through the inverters.
3.3.3 Transfer From Bypass Mode To Normal Mode
In bypass mode, press and hold the INVERTER ON key for two seconds. When the inverters are ready, the UPS
transfers to normal mode.
3.3.4 Transfer From Normal Mode To Maintenance Bypass Mode
When the UPS is operating in normal mode, use the following procedures to transfer the load from the inverter output
to the maintenance bypass.
Caution
Before performing this operation, read the messages on the LCD to be sure that bypass supply is normal and the inverters are
synchronous with it. If these conditions are not present, there is a risk of a short interruption in powering the load.
1. Press and hold the INVERTER OFF key on the right side of the operator control and display panel for two seconds.
The inverter indicator turns off, the status indicator turns yellow and an audible alarm sounds. The load is transferred
to the static bypass and the inverters turn off.
Note
Pressing the SILENCE ON/OFF key cancels the audible alarm, but leaves the warning message displayed until the appropriate
condition is rectified.
2. Close the maintenance bypass switch. The load is now on maintenance bypass.
Warning
If a module needs repair, wait about 10 minutes for the internal DC bus capacitors to discharge before removing the faulty module.