Emerson Liebert ICOM-DO Installation Manual Page 35

  • Download
  • Add to my manuals
  • Print
  • Page
    / 88
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 34
Refrigerant Connections
29
7.0 REFRIGERANT CONNECTIONS
NOTICE
Risk of oil contamination with water. Can cause equipment damage.
The piping must not be open to the atmosphere for extended periods because the Liebert CRV
requires POE (polyol ester) oil. POE oil absorbs water at a much faster rate when exposed to
air than previously used oils. Because water is the enemy of a reliable refrigeration system,
extreme care must be used when opening systems during installation or service. If water is
absorbed into the POE oil, it will not be easily removed and will not be removed through the
normal evacuation process. If the oil is too wet, it may require an oil change. POE oils also
have a property that makes them act as a solvent in a refrigeration system. Maintaining
system cleanliness is extremely important because the oil will tend to bring any foreign
matter back to the compressor.
The Liebert CRV can be connected to a condenser through either the top or bottom of the unit. The
unit is piped for connections at the top of the unit as shown in Figure 26, with provision for connec-
tion through the bottom of the unit.
Connecting through the bottom of the unit requires cutting the liquid and suction lines as shown in
Figure 27. Cutting these lines disconnects the top connections from the rest of the refrigeration system.
Air-cooled units are shipped with a holding charge of nitrogen.
7.1 Piping Guidelines—Air-Cooled Units
Indoor unit ships with a nitrogen holding charge; do not vent the evaporator until all refrigerant
piping is in place, ready for connection to the unit and condenser
Use copper piping with high temperature brazed joints
Isolate piping from building using vibration-isolating supports
Refer to Figures 30 and 31 for piping sizes
Refer to condenser installation manual for charging information
Install traps on hot gas (discharge) lines at the base of vertical risers and every 15 feet (4.6m) of
vertical rise.
See Table 9 for the allowable elevation difference between the condenser and the Liebert CRV.
Consult factory if piping run exceeds 150 feet (46m) equivalent length
Keep piping clean and dry, especially on units with R-410A refrigerant
Avoid piping runs through noise-sensitive areas
Do not run piping directly in front of airstream of any air conditioner
Refrigerant oil – do not mix oil types
Refer to ASHRAE Refrigeration Handbook for general, good-practice refrigeration piping.
!
WARNING
Risk of explosive discharge from high-pressure refrigerant. Can cause injury or death.
This unit contains fluids and/or gases under high pressure.
Relieve pressure before working with piping.
!
WARNING
Risk of refrigerant system rupture or explosion from over pressurization. Can cause
equipment damage, injury or death.
If a pressure relief device is not provided with the condenser unit, the system installer must
provide and install a discharge pressure relief valve rated for a maximum of 609psig (42bar)
in the high side refrigerant circuit. Do not install a shutoff valve between the compressor and
the field installed relief valve.
One or more additional pressure relief valves are required downstream of all field-installed
isolation valves. Do not isolate any refrigerant circuits from overpressurization protection.
Page view 34
1 2 ... 30 31 32 33 34 35 36 37 38 39 40 ... 87 88

Comments to this Manuals

No comments