Calibration Procedure of Optical Actuators
Press down on the photochopper shaft to disen-
gage the brake, releasing tension from the motor
mount. Use the INC button to pulse the actuator
to where the slide is just off of the mechanical
stop and there is no tension on the motor shaft.
10. Quickly press and release the blue button on the
actuator again. The red LED will now flash at a
slower rate, indication that the minimum slide
valve position (zero position) has been set.
11. Use the INC button on the Control Panel panel
to drive the slide to its maximum “mechanical
stop” position. Do not continue to run the ac-
tuator in this direction after the slide valve has
reached the stop. Doing so may cause dam-
age to the actuator or the slide valve. Press
down on the photochopper shaft to disengage
the brake, releasing tension from the motor
mount. Use the DEC button to pulse the actua-
tor to where the slide is just off of its mechanical
stop and there is no tension on the motor shaft.
12. Quickly press and release the blue button on the
actuator one more time. The red LED will stop
flashing. The actuator is now calibrated and
knows the minimum and maximum positions
of the slide valve it controls. Now the capacity
or volume channel of the PLC can be calibrated.
13. Use the DEC button to move the actuator to-
wards its minimum position while watching the
millivolt readout on the Control Panel screen.
Discontinue pressing the DEC button when the
millivolt reading the “Current” window above
the “Set Min” button is approximately 500 mil-
livolts.
14. Now use the DEC and INC buttons to posi-
tion the slide valve until a value close to 300
millivolts is on the screen. Then, press the
“Set Min” button in the capacity or volume
slide valve window to tell the controller that
this is the minimum millivolt position. Note:
The value in the “Current Cap” or “Current
Vol” window has no meaning right now.
Do not touch wires, may cause an
electrical shock!
8. Note: The “Slide calibration” screen on the Con-
trol Panel has a “Current” window, which displays
twice the actuator output voltage. This value,
(the % volume and the % capacity) displayed in
the “Current Vol” and Current Cap” Windows are
meaningless until calibration has been completed.
9. Use the DEC button on the Control panel to drive
the slide valve to its minimum “mechanical stop
position. Do not continue to run the actuator in
this direction after the slide valve has reached
the stop. Doing so may cause damage to the
actuator or the slide valve.
Remove Cover
Press Down On
Phot ochopper