VSG/VSSG • Compact Logix PLC Manual •Vilter/Emerson • 35391CL
· Minimum Run Capacity – The Minimum Run
Capacity is the minimum capacity the com-
pressor will be allowed to run at. When the
compressor is started, it will be loaded to the
Minimum Run Capacity control setpoint minus
5%. This is done to prevent the capacity control
from hunting if the load is not great enough to
keep the compressor capacity at the Minimum
Run Capacity setpoint. On a call for unloading,
the compressor will unload until it reaches the
Minimum Run Capacity control setpoint. It will
remain there until the suction pressure reduces
and the compressor cycles off on the Suction
Pressure On/Off control setpoint.
· Volume Slide Adjustment Factor – This value is
normally zero (0) and will not require changing.
However, if the system operating conditions
show the volume ratio is not at the optimum
value for the system, this value can be adjusted
up or down to permit the most efficient position-
ing of the volume slide valves. To determine the
value to enter, first ensure that the system is in
a steady operating state and place the volume
side in manual. NOTE: The volume position set-
ting and increase the volume side position slowly
until the lowest amperage level is achieved. If the
amperage level rises instead of falls, decrease the
volume slide position until the lowest amperage
is achieved.
Record the differential from the original position.
This will then be adjustment factor to enter for
our system. NOTE: Negative numbers can be
used for this setting. This setpoint is active on a
drop in capacity below the Capacity Slide Adjust-
ment Range cut-in (ON) setting. The adjustment
is disabled when capacity rises above the Adjust-
ment Range OFF setting. Normally, the “ON-Off”
set points should both be set at 100%, so the
volume side adjustment factor will be applied
over the full range of 0 to 100%
· Current Transformer Ratio – The value entered
must agree with the Current Transformer Ratio
on the current transformer being used. The
current transformer is mounted in the compres-
sor motor conduit box. The ratio is stated as
the ratio of measured current to a nominal full
scale current in the secondary of 5 amps; only
the first of these is entered. For example, if the
ratio reads 250/5, enter 250.
· Low Suction Pressure Load Limit – Active in
Discharge Pressure Capacity Control mode only.
These setpoints limit the compressor from load-
ing at low suction pressure conditions. They
override the discharge pressure capacity control
setpoints. When the OFF setpoint is reached
(at or below setpoint), the compressor will not
be allowed to load any further. If the suction
pressure continues to fall, the capacity of the
compressor will decrease when the suction
pressure is at or below the ON set point. It will
stop decreasing when the suction pressure rises
to a point that is just below the ON set point.
· Forced Unload – Capacity Decrease (%/sec) –
This is the rate at which the Main Motor VFD will
drop when there is a Forced Unload condition
present in the Compressor.
· Forced Unload – VFD Transition Point to Capacity
Decrease (%/sec) – This is VFD speed at which
the physical capacity slide will begin to decrease
while there is a Forced Unload condition present
in the Compressor.