VSG/VSSG • Compact Logix PLC Manual •Vilter/Emerson • 35391CL
Diagnostics Force Output
To force an output, a user with high level access must be logged on first. Without sufficient access, the out-
puts display without force buttons. Touch the Logon button or Set button to prompt the Logon screen. At
the Logon screen, enter the user name (case sensitive) then the user’s password (case sensitive) then press
the <-| enter button. The currently logged in user’s name displays on the Logon screen, on the Logon button
(on the main menu and on the Setup screen.
Once a user with sufficient access is logged on, force buttons appear.
To force an output on, touch its button. The “Main Compressor Motor Starter*” button and “Starter Reset”
button are momentary-on buttons while the others are maintained buttons. Forced-on buttons display green.
On/Off output status displays to the right of each button.
Return all maintained buttons to their off (grey color) state before exiting this screen. Exiting this screen does
not automatically remove forces.
WARNING: Be sure to remove all outputs from Forced-On mode before exiting this screen!