1.4 Major Components
The operating principle of the UPS is illustrated in Figure 7.
Figure 7 Operating principle diagram
The UPS is composed of utility input, TVSS and EMI/RFI filters, rectifier/PFC, inverter, battery
charger, DC-to-DC converter, battery, dynamic bypass and UPS output.
Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters
The Liebert GXT4 has surge protection and filters that protect the connected load from power surges,
electromagnetic interference (EMI) and radio frequency interference (RFI). These features can
minimize any surges or interference present in the utility power. The filters also prevent surges or
interference generated by the UPS from adversely affecting devices connected on the same branch as
the UPS.
Rectifier/Power Factor Correction (PFC) Circuit
In normal operation, the Liebert GXT4’s rectifier/power factor correction (PFC) circuit converts utility
power to regulated DC power for use by the inverter while ensuring that the wave shape of the input
current used by the UPS is near ideal. Extracting this sinewave input current achieves two objectives:
Efficient power use by the UPS
Reduced reflected harmonics
This results in cleaner power being available to other devices in the building not being protected by
the Liebert GXT4.
Inverter
In normal operation, the Liebert GXT4’s inverter utilizes the DC output of the PFC to produce
precise, regulated sine wave AC power. When utility power fails, the inverter receives DC power from
the DC-to-DC Converter. In either operation mode, the UPS inverter is online, continuously
generating clean, precise, regulated AC output power.
Battery Charger
The battery charger utilizes energy from the utility power and precisely regulates it to continuously
float charge the batteries. The batteries are being charged whenever the Liebert GXT4 is plugged in,
even when the UPS is not turned On.
TVSS
EMI/RFI
Input
Filter
Inverter
DC-DC
Converter
Battery
Charger
Battery
Dynamic
Bypass
L
G
N/L2*
G
L
Programmable
Outlet
Group 1
General
Outlet
Group
Programmable
Outlet
Group 2
General
Outlet
(3000 VA Only)
N/L2*
EMI/RFI
Output
Filter
* NOTE: ONLY the GXT4-3000 RT208 model (208V) requires L 2 (L6-20P).
All other models covered in this manual are 120 V L-N wired
Rectifier/
PFC