71
Reference Manual
00809-0200-4728, Rev RA
Section 5: Operation and Maintenance
April 2015
Operation and Maintenance
5.4.1 Recall factory trim—sensor trim
The Recall Factory Trim—Sensor Trim feature allows the restoration of the as-shipped factory
settings of the analog output trim. This command can be useful for recovering from an
inadvertent trim, incorrect Plant Standard or faulty meter.
Recall factory trim – sensor, using a Field Communicator
From the HOME screen, enter the Fast Key sequence and follow the steps within the Field
Communicator to complete the Sensor Trim.
Recall factory trim – sensor, using AMS Device Manager
1. Right click on the device and select Service Tools.
2. On the Sensor Calibration tab, select the Restore Factory Calibration.
3. Follow the screen prompts through the restoring of the calibration settings.
Recall factory trim – sensor, using LOI
Reference the below image for where to find Recall Sensor Trim in the LOI menu.
Figure 5-3. Recalling the Sensor Trim with the LOI
5.4.2 Active calibrator and EMF compensation
The transmitter operates with a pulsating sensor current to allow EMF compensation and
detection of open sensor conditions. Because some calibration equipment requires a steady
sensor current to function properly, the “Active Calibrator Mode” feature should be used when
an Active Calibrator is connected. Enabling this mode temporarily sets the transmitter to
provide steady sensor current unless two sensor inputs are configured.
Disable this mode before putting the transmitter back into the process to set the transmitter
back to pulsating current. “Active Calibrator Mode” is volatile and will automatically be disabled
when a master reset is performed (through HART) or when the power is cycled.
Device Dashboard Fast Keys
3, 4, 4, 2
CALIBRATCALIBRAT
DAMPING
VARIABLE MAP
TAG
ALM SAT VALUES
PASSWORD
....
VIEW CONFIG
SENSOR CONFIG
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXTENDED MENU
EXIT MENU
SENSOR 1 CALIB
SENSOR 2 CALIB*
ANALOG TRIM
FACTORY RECALL
FACTORY RECALL
BACK TO MENU
EXIT MENU
....