Reference Manual
00809-0200-4728, Rev RA
Section 2: Configuration
April 2015
Configuration
2.6 Basic configuration of the transmitter
The 644 must be configured for certain basic variables in order to be operational. In many cases,
all of these variables are pre-configured at the factory. Configuration may be required if the
transmitter is not configured or if the configuration variables need revision.
2.6.1 Mapping the HART variables
Mapping the HART variables with a Field Communicator
The “Variable Mapping” menu displays the sequence of the process variables. Select the
sequence below to change this configuration. The 644 single sensor input configuration screens
allow selection of the primary variable (PV) and the secondary variable (SV). When the Select PV
screen appears Snsr 1 must be selected.
The 644 dual-sensor option configuration screens allow selection of the primary variable (PV),
secondary variable (SV), tertiary variable (TV), and quaternary variable (QV). Variable choices
are Sensor 1, Sensor 2, Differential Temperature, Average Temperature, Terminal Temperature,
and Not Used. The 4-20 mA analog signal represents the Primary Variable.
From the HOME screen, enter the Fast Key sequence.
Mapping the HART variables with AMS Device Manager
1. Right click on the device and select the Configure menu.
2. In the left navigation pane choose Manual Setup then on the HART tab.
3. Map each variable individually or use the Re-map Variables method to guide you
through the re-mapping process.
4. Select Apply when complete.
Mapping the HART Variables with LOI
Follow flow chart to select the desired mapped variables. Use the SCROLL and ENTER buttons to
select each variable. Save by selecting SAVE as indicated on the LCD screen when prompted. See
Figure 2-4 on page 16 for an example of a mapped variable with the LOI.
Figure 2-4. Mapping Variables with LOI
Device Dashboard Fast Keys
2, 2, 8, 6
CALIBRAT
DAMPING
VARIABLE MAP
VARIABLE MAP
TAG
ALM SAT VALUES
PASSWORD
....
RE-MAP PV
RE-MAP 2V
RE-MAP 3V
RE-MAP 4V
....
VIEW CONFIG
SENSOR CONFIG
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENUEXTENDED MENU
EXIT MENU