Emerson ZB Copeland Scroll Service Manual Page 14

  • Download
  • Add to my manuals
  • Print
  • Page
    / 47
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 13
12
ZB Series
Installation and piping arrangement
Electrical connection
Power supply voltage and connecting terminals
Please note the direction of the connecting terminals in the
connecting box (single-phase power: R, S, C; three-phase power: T1;
T2; T3). To ensure normal start and operation of the compressor, the
power supply voltage should not drop more than 10% below the rated
voltage for the compressor.
Starting characteristics of the single-phase compressor
The single-phase scroll compressor is equipped with a permanent
fractional capacitor motor (PSC). Auxiliary starting equipment is
unnecessary for most applications. But auxiliary starting equipment is
necessary for some applications (for example, if the starting voltage
is lower). In the latter case, a starting capacitor and a secondary relay
may be used at start-up.
Rotation direction of three-phase compressor
The compression process of the scroll compressor occurs only in one
direction. The single-phase compressor starts and operates based on a
correct direction of rotation (except under such conditions where the
power supply is abruptly cut off). The direction of the rotation for the
three-phase compressor depends on the phase sequence of the power
supply. Hence, the compressor has a 50% chance of "reverse-rotation".
When the installation operation is carried out at-site, the correct
direction of the rotation can be judged by discharge pressure increase
and suction pressure decrease. However, if the compressor is running
in reverse direction, the compressor will give out an abnormal noise
and the current draw will clearly be lower than the rated value as well.
A brief reverse-rotation is harmless to the compressor. But a reverse-
rotation for long periods can damage the compressor. Equipment
manufacturers can place a phase sequence protection module in the
control circuit to ensure that the machine will not operate in case of
incorrect phase sequence. Since there is a 50-50 chance of connecting
power in such a way as to cause rotation in the reverse direction, it is
important to include notices and instructions in appropriate locations
on the equipment to ensure proper rotation direction is achieved
when the system is installed and operated.
Instantaneous Power Shut-Off
Instantaneous shut-off (power-off time is below 0.5 sec.) can lead to
change in the direction of rotation of the single-phase compressor.
After shut-off, the compressor operation will last several minutes
in the reverse direction until the internal motor protector of the
compressor is triggered. The compressor will not be affected in
this process. After the motor protector resets, the compressor
will re-start and operate in the correct direction of rotation.
Copeland recommends using a relay that can respond to this
instantaneous shut-off. The relay helps to re-start the compressor
automatically after a time-delay of two minutes. Three-phase
compressors do not need a relay.
High-voltage test
The motor of the refrigerating scroll compressor is in a casing. After
charging refrigerant into the system, the motor could be immersed
into the liquid refrigerant. When the liquid level in the casing is
higher, the result of the high-voltage test could indicate a higher
current value, because the conductivity of the liquid refrigerant is
higher than that of the gas or the lubricating oil. This phenomenon
will only happen when the compressor motor is entirely immersed
in the liquid refrigerant, but there is no safety issue.
Evacuation (drying)
The system must be evacuated after current leakage test. A
vacuum pump must be used to evacuate. The compressor
should never be used for self-evacuation. To evacuate, it is
suggested that the vacuum pump be connected to the high and
low-side evacuation valves with copper tube or high-vacuum
hoses (with internal diameter of at least 8mm). The sum of the
sectional areas of all connecting pipes should not be below the
sectional area of the inlet pipe for the vacuum pump.
Page view 13
1 2 ... 9 10 11 12 13 14 15 16 17 18 19 ... 46 47

Comments to this Manuals

No comments