ZB Series
Application guide
Installation and piping arrangement
Installation of the compressor should be done according to the
service conditions. The selected installation and piping design
should dampen the transmission of noise and vibration as far as
possible. Please see also the following table for tightening torques:
Reference table for tightening torque
Torque (N.m)
Rotalock screw valve 3/4''-16UN 40-50
Rotalock screw valve 1 1/4''-12UN 100-110
Rotalock screw valve 1 3/4''-12UN 170-180
Rotalock screw valve 2 1/4''-12UN 190-200
Flange with M16 stud 102-113
Oil level sight glass 25-25.5
5/16'', M9 installation stud Maximum 27
Soft foot 12-14
Connecting screw in terminal box 2.5-2.6
Mounting
The single-compressor-condenser unit makes use of soft rubber
grommets for mounting. When the compressors are used for
tandem operation, they are mounted by means of steel spacers or
two steel rails. This rigid mounting keeps the interconnecting tubing
stresses to a minimum. The tandem assembly should be mounted on
rubber isolating grommets to the unit base pan. Both compressors
must be at the same level to prevent oil from migrating to the lowest
compressor through the oil equalization line.
Pipeline
During installation, great care should be taken to keep the
piping lines of the refrigerating equipment extremely clean. In
principle, the refrigerating equipment should always have clean
and dry pipelines, and there should not be any scale, rust and
phosphate layer on it. Dry nitrogen must be charged in the
pipeline during welding. To prevent the welding joints in the
pipeline from producing foul, the welding temperature must be
carefully controlled. The welding operation should not be
carried out on pipeline that contains refrigerant (even if the
refrigerant is not under pressure), because the heating of
refrigerant, oil and air will form a toxic gas. The pipeline design
must ensure that, even at part load, the lubricating oil returns
to the compressor despite low gas flow velocity in the suction
and discharge pipes.