Emerson CP400 Instruction Manual Page 13

  • Download
  • Add to my manuals
  • Print
  • Page
    / 20
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 12
CP400 Series
13
Step 4:
Once the operator feels the click of the re-latch
occurring, the reset button (key 30) should be
pushed completely back into its original position.
Shutdown
Installation arrangements may vary, but in any
installation it is important that the valves be opened or
closed slowly and that the outlet pressure be vented
before venting inlet pressure to prevent damage caused
by reverse pressurization of the regulator. The steps
below apply to the typical installation as indicated.
1. Open valves downstream of the regulator.
2. Slowly close the upstream block valve.
3. Pressure releases downstream.
Maintenance and Inspection
!
WARNING
To avoid personal injury or equipment
damage, do not attempt any
maintenance or disassembly without
rst isolating the regulator from system
pressure and relieving all internal
pressure as described in “Shutdown”.
Regulators that have been disassembled
for repair must be tested for proper
operation before being returned to
service. Only parts manufactured by
Regulator Technologies should be used
for repairing Fisher
®
regulators. Restart
gas utilization equipment according to
normal startup procedures.
Due to normal wear or damage that
may occur from external sources, this
regulator should be inspected and
maintained periodically. The frequency
of inspection and replacement of parts
depends upon the severity of service
conditions or the requirements of local,
state and federal rules and regulations.
Periodic inspection must be performed
on the CP400 Series that include
the Integral Monitor or slam-shut
overpressure protection modules to
ensure that they protect the downstream
system in the event the primary regulator
losses pressure control. This inspection
must test that the Integral Monitor or
slam-shut functions as intended. The
frequency of this inspection must be at
intervals not exceeding 15 months, but at
least once each calendar year.
When maintenance is required on the
slam-shut device, refer to the Type VSX4
Instruction Manual, part number
D103127X012. When maintenance is
required on the Integral True-Monitor™
device, refer to the Type TM600
Integral Monitor Instruction Manual, part
number D103126X012.
To Replace Main Diaphragm
1. Disconnect the tubing connector (key 29, Figure 8)
from the loading pressure regulator.
2. Remove closing cap (key 60, Figure 8) and
unscrew the nut (key 47). Unthread the upper
spring seat (key 42) using a at head screwdriver.
Remove the closing spring (key 38).
3. Unscrew and remove the cap screws (key 15) and
nuts (key 16) and lift the spring case (key 1) with
attached loading regulator off the lower casing
(key 9) and the closing stem (key 44).
Note
When disassembling a CP400 Series
regulator, lift the upper spring case
(key 1) and the loading pressure
regulator straight up in order to avoid
hitting the stem (key 44).
4. Lift the diaphragm assembly (key 55) slightly so
that the pusher post (key 51) can release the valve
lever (key 10).
5. Hold the pusher post (key 51) xed while
unscrewing the closing stem (key 44) from the
pusher post (key 51). Remove the diaphragm
retainer (key 43) and diaphragm head (key 55).
The diaphragm can now be removed.
6. Reassemble in the reverse order of the above
procedure. Before tightening the cap screws (key 15)
or closing stem (key 44) into the pusher post (key 51),
place the loosely-assembled diaphragm assembly
(key 55) into position in the lower casing (key 9), the
arch or bow of the diaphragm should be towards the
diaphragm head and lower casing (see Figure 8).
Ensure that the pusher post (key 51) is hooked on
the lever (key 10). Rotate the diaphragm (key 55) so
that the diaphragm and lower casing (key 9) holes
are aligned.
Page view 12
1 2 ... 8 9 10 11 12 13 14 15 16 17 18 19 20

Comments to this Manuals

No comments