Operating Instructions
29
4.6 Liebert LDMF (Optional)
If the Liebert RDC is equipped with the optional Liebert LDMF, the monitoring unit is On whenever
power is supplied to the unit. The Liebert LDMF is factory-configured for 1-pole, 20A branch break-
ers. Alarms, alarm setpoints, circuit breaker names and circuit breaker ratings are all field-adjust-
able through the DB9 connector (LDMF SETUP port next to the panelboard main circuit breaker).
For more information, refer to 1.8 - Liebert LDMF
Current Transformer (CT) Installation for
branch circuit breaker connections, 1.9 - Liebert LDMF Communication for communication
options and connections and the Liebert LDMF user manual (SL-20200).
The Liebert LDMF has an optional local display that allows users to view monitoring information for
the panelboard main circuit breaker as well as each individual branch circuit breaker. Alarm data can
be viewed from the local display for up-to-date breaker status.
Figure 24 Liebert LDMF optional local display
The Liebert LDMF monitors and displays the parameters listed in Table 1.
Table 1 Liebert LDMF monitored parameters
Parameters
Panelboard
branch
circuit breaker
Displayed and monitored for each:
Panelboard main circuit breaker
and Square D I-Line
®
panelboard
Square D I-Line
panelboard
circuit breaker
Subfeed
circuit
breaker
Voltage
Line-to-line
——
Line-to-neutral
——
Phase Current
✔✔
Neutral Current
✔✔
Ground Current
✔✔
kVA
✔✔
kW
✔✔
kW-Hours
✔✔
Percent Load
✔✔
Power Factor
✔✔
Crest Factor
✔✔
Total Harmonic Distortion (THD)
Voltage THD
✔✔
Current THD
✔✔
Circuit identification and status of each breaker are also displayed.